Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Issued
Type:
Commercial Building
Address:
1 E TOOLE AV
Apply Date:
06/27/2023
Applicant:
Chris Leighton
Description:
Adding an ADA accessible ramp No change to existing building

Permit Reviews

Permit Number - TC-COM-0623-01590
Permit Status: Issued
Permit Description: Adding an ADA accessible ramp No change to existing building
Start Date Submittal Complete Date Status  
04/24/2024 COMMERCIAL REVIEW - FULL v.1 04/24/2024 IN REVIEW Review Details
07/29/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.1 07/29/2024 APPROVED Review Details
03/21/2024 COMMERCIAL REVIEW - FULL v.1 04/01/2024 REQUIRES RESUBMIT Review Details
07/17/2024 BUILDING DEFERRED SUBMITTAL REVIEW v.1 07/18/2024 APPROVED Review Details
04/01/2024 COMMERCIAL REVIEW - FULL v.1 04/24/2024 IN REVIEW Review Details
04/25/2024 RESTAMP - COMMERCIAL v.1 04/25/2024 APPROVED Review Details
06/29/2023 COMMERCIAL REVIEW - FULL v.1 08/03/2023 APPROVED Review Details
04/24/2024 COMMERCIAL REVIEW - FULL v.2 04/25/2024 APPROVED Review Details

Conditions

Permit Number - TC-COM-0623-01590
Permit Status: Issued
Permit Description: Adding an ADA accessible ramp No change to existing building
Date Description Comments
08/10/2023 The Contractor you have added to your permit cannot be verified. Please contact staff to have the ROC number added to the account.
06/29/2023 Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit.
04/19/2024 SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED.
04/19/2024 Vince Catalano - Working with TEP to relocate guy wire at ACCESS TO A PUBLIC WAY from STAIR, southwest corner of building.
08/03/2023 IBC 1008 Illumination level at Means of Egress shall not be less than 1 footcandle at the walking surface with emergency power of not less than 90 minutes duration from storage batteries or on-site generator.
04/19/2024 SPECIAL INSPECTION FOR OUTDOOR LIGHTING IS REQUIRED.
08/03/2023 IBC 1012 RAMP RUNNING SLOPE NOT STEEPER THAN 1:12 CROSS SLOPE 1:48 MAXIMUM, VERICAL RISE 30 INCHES MAXIMUM, 36 INCHES CLEAR WIDTH BETWEEN HANDRAILS, MINIMUM 80 INCHES HEADROOM, LANDING AT TOP AND BOTTOM 60 INCHES LONG AND THE SAME WIDTH AS RAMP (60 INCHES X 60 INCHES WHERE CHANGE IN DIRECTION OCCURS AT LANDING) WITH SLOPE NOT STEEPER THAN 1:48 IN ANY DIRECTION, PROJECTIONS INTO RAMP AND LANDING PROHIBITED, MATERIALS USED SHALL BE SLIP -RESISTANT, HANDRAILS REQUIRED BOTH SIDES WHERE OVER 6 INCHES OF RISE OCCURS AT 34 TO 38 INCHES HEIGHT WITH CROSS SECTION 1-1/4 TO 2 INCHES DIAMETER TYPE I EXTENDING 12 INCHES MINIMUM HORIZONTALLY ABOVE THE TOP AND BOTTOM LANDINGS. EDGE PROTECTION CAN UTILIZE A WALL, A MINIMUM 4 INCH HIGH CURB, A RAIL OR BARRIER PREVENTING PASSAGE OF A 4 INCH DIAMETER SPHERE OR EXTEND RAMP/LANDING SURFACE 12 INCHES MINIMUM BEYOND INSIDE FACE OF HANDRAIL. GUARDS REQURED ALONG OPEN SIDED WALKING SURFACES THAT ARE 30 INCHES MEASURED VERTICALY BELOW ANY POINT WITHIN 36 INCHES HORIZONTALLY TO THE WALKING EDGE (SEE IBC 1015).
04/16/2024 Property must be purchased from Right Of Way prior to issuance.
04/19/2024 A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.
04/17/2024 Steel Stairway Designs and calculations must be submitted, approved and stairway to be installed on site, with means of egress complete, prior to final inspections, T C of O and C of O of permit #TC-COM-1123-02704 Tenant Space/Building.
09/13/2023 There are 3 openings into the basement (the middle one looks like not for fresh air opening), (the right opening is clear away from the beginning of the ramp) & (however the opening on the left has been covered by the ramp, this has to be addressed to allow outside air for the basement. VINCED CATALANO RESPONSE: 09/13/23 That vent has been closed for many years from the inside, there is plenty of ventilation from the other sides of the building, see pictures. (see copy of email with photos that was uploaded with the rest of the permit files called "Ventilation at basement TC-COM-0623-01590 (1 E TOOLE AV").
08/03/2023 SPECIAL INSPECTION FOR WELDING REPORT IS REQUIRED.

Outstanding Inspections

Permit Status: Issued
Permit Number: TC-COM-0623-01590
Permite Description: Adding an ADA accessible ramp No change to existing building
Total Outstanding Inspections - 3
Last Inspection Date Description Inspector Results Comments
07/17/2024 TRSP - ROW - Final/Close-Out N/A Re-inspection required
07/18/2024 ENGR Engineering Final N/A Partial Pass 1) On the west side of this building there are 2 pipes or fittings that stick out of the building and the existing grade too far into the pedestrian pathway creating trip hazards. These will either need to be removed or cut.
2) Roof drainage needs clarification or correction. The correct drain locations must be determined for the Roof Drainage Pipes, and where it may need to be relocated so that it does not deposit water within the 10-year Storm directly onto a Pedestrian Pathway. The Canopy above the ramp that will deposit water directly onto the ramp which is not allowed per our City Codes. This area will need roof gutters to transport this water to an area where it can be released so that it does not deposit water directly onto the Pedestrian Pathways.
3) The handrail extensions have not been provided on the west end of the ramp, and the extensions have not been completed on the east side of the ramp per the Code Specification. The Code that we are utilizing is ICC A 117.1–2009, section 505.10.1 Top and Bottom Extension at Ramps. For this code, the wrap around extension should be 12 inches from the last supporting post to the inside of the outer wraparound. The wraparound itself should be continuous and be welded back into the supporting member at the very end of the handrail to complete the loops as shown per this detail in the Specifications.
4) The Landing at the bottom of the Ramp does not have the correct slope and grade, they exceed the maximum percent of 2% or less in all directions. Also, the Handrail on the southside of the Ramp has been extended approximately 5 feet to the east of the ramp due to a trip hazard in the adjacent area. This Modification will require that the landing now must be started from the end of the east rail extension for 60 inches to allow for the proper change of direction as required by the code. Coordination with Department of Transportation will be required to modify these areas to conform with ADA Requirements.
07/18/2024 COT - LCBU - Preslab N/A Not Ready During the inspection, the following items were noted as being incorrect, and will need to be pleaded and approved prior to the final inspection of this permit.
1) On the west side of this building to trip hazards have been noticed in an area approximately 20 feet north of the south west corner of the building. These are pipes or fittings that stick out too far into the pedestrian pathway that need to either be removed or cut off low grade in buried.
2) A question has been raised about the roof drainage on this building at two different locations. One is at the north west corner of the building. The other is at the south east corner of this building 6 inch drain pipes are noted at ground level that appear to be drain pipes for the roof. If these are correct, they will be redirected. To another area for the Riddick drainage to be deposited outside of the pedestrian pathway. At both locations, there is above grade roof drainage opening that has deposited water directly onto pedestrian, pathways, and stairways. That will need to be redirected to a different location. Provide details and drawings of the changes that will be made to the roof drainage system for approval to the city of Tucson prior to any final inspections for the site.
3) on the ramp, the inspectors have noted that the extensions have not been provided on the west end of the ramp, according to current codes and standards, and the extensions have not been completed on the east side of the ramp to the specifications of the coats. The code that we are considering is ICC a 117.1–2009, section 505.10.1 top and bottom extension at reps.

Completed Inspections

Permit Status: Issued
Permit Number: TC-COM-0623-01590
Permit Description: Adding an ADA accessible ramp No change to existing building
Total Completed Inspections - 1
Date Description Inspector Results Comments
07/18/2024 COT - FCON - Fire - Final Passed

Documents

File Name Document Type  
1 E TOOLE SI REPORT - PERMIT 01590-2024-07-17_V1.PDF DOCUMENTS VIEW
CONS-1_A-1 THRU S1 1 E TOOLE RAMP 6-13-23_V1.PDF DOCUMENTS VIEW
CONS-6_A-1 THRU E1 1 E TOOLE RAMP 4-23-24_V5.PDF DOCUMENTS VIEW
CONS-6_A-1 THRU E1 1 E TOOLE RAMP 4-23-24_V5.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
COFT - PDSD - PERMIT CARD.PDF DOCUMENTS VIEW
CONS-6_A-1 THRU E1 1 E TOOLE RAMP 4-23-24_V5.PDF DOCUMENTS VIEW
CONS-1_A-1 THRU S1 1 E TOOLE RAMP 6-13-23_V1.PDF DOCUMENTS VIEW
CONS-6_A-1 THRU E1 1 E TOOLE RAMP 4-23-24_V5.PDF DOCUMENTS VIEW
SPECIAL INSPECTION CERTIFICATE (7)-2023-06-27_V1.PDF DOCUMENTS VIEW
STRUCTURAL CALCULATIONS (12)_V1.PDF DOCUMENTS VIEW
CONS-1_A-1 THRU S1 1 E TOOLE RAMP 6-13-23_V1.PDF DOCUMENTS VIEW
SPECIAL INSPECTION CERTIFICATE (7)-2023-06-27_V1.PDF DOCUMENTS VIEW
STRUCTURAL CALCULATIONS (12)_V1.PDF DOCUMENTS VIEW