Permit: TC-COM-0225-00267
Permit Details
Status:
Complete
Type:
Commercial Building
Address:
6565 E CARONDELET DR UNIT 335
Address NEW:
6565 E CARONDELET DR UNIT 335
Apply Date:
02/10/2025
Applicant:
Allysia Higbee
Description:
Tenant improvement of a 2089 sq.ft. medical office in an existing bldg
Permit Reviews
Permit Number - TC-COM-0225-00267
Permit Status: Complete
Permit Description: Tenant improvement of a 2089 sq.ft. medical office in an existing bldg
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 02/11/2025 | COMMERCIAL REVIEW - LIMITED v.1 | 02/25/2025 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-COM-0225-00267
Permit Status: Complete
Permit Description: Tenant improvement of a 2089 sq.ft. medical office in an existing bldg
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 02/25/2025 | AIR BALANCING REPORT IS REQUIRED. |
Conditions
Permit Number - TC-COM-0225-00267
Permit Status: Complete
Permit Description: Tenant improvement of a 2089 sq.ft. medical office in an existing bldg
| Date | Description | Comments |
|---|---|---|
| 02/11/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. | |
| 02/11/2025 | Separate submittal to PC RWRD is required for new connections to sewer, new water meters and upsized water meters. For review and assessment: apply online at https://permits.pima.gov/ or contact us at sewer@pima.gov, (520) 724-9900. |
Outstanding Inspections
Permit Status: Complete
Permit Number: TC-COM-0225-00267
Permite Description: Tenant improvement of a 2089 sq.ft. medical office in an existing bldg
Total Outstanding Inspections - 4
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/13/2025 | COT - FCON - Alarm - Final | N/A | Not Applicable | |
| 08/13/2025 | BULD - Electrical Clearance | N/A | Not Applicable | |
| 08/13/2025 | COT - FCON - Sprinkler - Final | N/A | Re-inspection required | Need sprinkler coverage in closet, evaluation, plans and permit by sprinkler contractor |
| 08/20/2025 | COT - FCON - Fire - Final | N/A | Partial Pass | Exit sign shall be illuminated |
Completed Inspections
Permit Status: Complete
Permit Number: TC-COM-0225-00267
Permit Description: Tenant improvement of a 2089 sq.ft. medical office in an existing bldg
Total Completed Inspections - 17
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/15/2025 | COT - LCEL - Electrical Intermediate | Passed | ||
| 07/15/2025 | COT - LCPL - Plumbing Intermediate | Passed | ||
| 07/15/2025 | COT - LCBU - Framing | Passed | ||
| 07/15/2025 | COT - HCME - Mechanical Intermediate | Passed | ||
| 07/15/2025 | COT - LCPL - Rough Soil | Passed | ||
| 07/21/2025 | COT - LCEL - Electrical Above Ceiling | Passed | ||
| 07/21/2025 | COT - HCME - Mechanical Above Ceiling | Passed | ||
| 07/21/2025 | COT - HCPL - Plumbing Above Ceiling | Passed | ||
| 08/13/2025 | COT - BULD - SWG Clearance | Passed | ||
| 08/13/2025 | COT - LCBU - Building Final | Passed | ||
| 08/13/2025 | COT - LCEL - Electrical Final | Passed | ||
| 08/13/2025 | COT - LCME - Mechanical Final | Passed | ||
| 08/13/2025 | COT - LCPL - Plumbing Final | Passed | ||
| 08/13/2025 | ENGR Engineering Final | Passed | Site is clear and accessible, in accordance with approved plans. | |
| 08/13/2025 | TRSP - ROW - Final/Close-Out | Passed | ||
| 08/20/2025 | COT - FCON - Sprinkler - Final | Passed | ||
| 08/21/2025 | COT - FCON - Fire - Final | Passed |