Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: TC-COM-0125-00020
Permit Details
Apply Date:
01/03/2025
Applicant:
Chandler Macomber
Description:
Replacement for 2 ton 14 SEER gas split system per apartment. Outdoor condenser on rooftop stands and indoor 80% AFUE gas furnace and coil in mechanical closet.
Permit Reviews
Permit Number - TC-COM-0125-00020
Permit Status: Issued
Permit Description: Replacement for 2 ton 14 SEER gas split system per apartment. Outdoor condenser on rooftop stands and indoor 80% AFUE gas furnace and coil in mechanical closet.
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
01/06/2025 | COMMERCIAL PDSD SIMPLE REVIEW v.1 | 01/10/2025 | APPROVED |
Outstanding Activity Conditions
Permit Number - TC-COM-0125-00020
Permit Status: Issued
Permit Description: Replacement for 2 ton 14 SEER gas split system per apartment. Outdoor condenser on rooftop stands and indoor 80% AFUE gas furnace and coil in mechanical closet.
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
01/17/2025 | TC-COM-0125-00020 - Regarding this permit. 1. It has been brought to our attention that you don’t intend to provide the required ventilation for the subject space/dwelling. 2. Apparently, While the unit is only 4911 BTUH below the total sensible gain, there is no load shown for the required ventilation. 3. Please do ensure that the required ventilation meets the Code Requirement. If as a result of this means installing a bigger unit to meet the Code Requirement then you may have to follow through with this. 4. Required by Section 503.1.2, IECC 2018. |
Conditions
Permit Number - TC-COM-0125-00020
Permit Status: Issued
Permit Description: Replacement for 2 ton 14 SEER gas split system per apartment. Outdoor condenser on rooftop stands and indoor 80% AFUE gas furnace and coil in mechanical closet.
Date | Description | Comments |
---|---|---|
01/06/2025 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. Contractor must have a TDC Online account and be added to the permit as a contact. |