Permit: T99CM05160
Permit Details
Apply Date:
10/28/1999
Applicant:
CHICANOS POR LA CAUSA
Description:
SFR:TD#14-34-57
Completed Inspections
Permit Status: Final
Permit Number: T99CM05160
Permit Description: SFR:TD#14-34-57
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/1999 | ROOF NAILING | JRIVA | Approved | IVRS - Inspection 0999* |
| 12/22/1999 | ROOF NAILING | JRIVA | Approved | ADDTL COMMS - 1. INCORRECT HOLD DOWNS AT CARPORT STORAGE-REQUIRES HPAHD 22 5 PAAD-42 INSTALLED. PROVIDE INGINEER AND C.O.T. APPROVED REPAIR. 3. 15/10 NOT COMPLIED WITH. 4. 12/10 NOT COMPLIED WITH. 5. ST 2115 STRAPS MISSING AT CARPORT. 5. ST 2115 STRAPS MISSING AT CARPORT. 12. RIPPERS LESS THAN 12 ON ROOF NOT ALLOWED UNLESS EDGES BLOCKED. NOTE: SHEAR WALL 4 REQUIRES SHEATHING TO ROOF DECK. |
| 12/22/1999 | EXT METAL CLIPS/EXT SHEATHING | JRIVA | Approved | IVRS - Inspection 0999* |
| 12/22/1999 | EXT METAL CLIPS/EXT SHEATHING | JRIVA | Approved | ADDTL COMMS - 7. CLIP ALL BEARING STUDS TOP AND BOTTOM. NOT EVERY OTHER STUD. 8. 4 EACH PAHD 42 HOLD DOWNS MISSING OR IN WRONG LOCATIONS AT REAR OF HOUSE. PROVIDE ENGINEERS AND C.O.T. APPROVED REPAIR. 9. BEDROOM 2 REQUIRES 2X10 HEADER. 10. SHEAR WALL 2 REQUIRES BLOCKING. 11. CARPORT NOT PER 13/10 BUILD TO PLAN OR HAVE ARCHITECT REVISE PLAN AND HAVE APPROVED BY CITY OF TUCSON. |