Permit: T99CM04384
Permit Details
Apply Date:
09/13/1999
Applicant:
BROWN ERIK
Description:
ADDITION:DINING ROOM
Completed Inspections
Permit Status: Final
Permit Number: T99CM04384
Permit Description: ADDITION:DINING ROOM
Total Completed Inspections - 7
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/1999 | EXCAVATION/LAYOUT REBAR & ZON | RCHAVEZ | Approved | ADDTL COMMS - EXCAVATION LAYOUT OKAY TO CONTINUE. SITE PLAN NEEDS TO BE REVISED. CARPORT EXTENDED TO PROPERTY LINE, ALSO STORAGE ADD-ON ATTACHED IS NOT ON SITE PLAN. |
| 10/14/1999 | REINFORCED MASONRY PRE-GROUT | RFREIDIN | Approved | ADDTL COMMS - 2X 8 FOR PORCH TO BE REVISED ON PLAN OR FOR 13 8 MAX. |
| 11/09/1999 | MECHANICAL - FINAL | RFREIDIN | Approved | IVRS - Inspection 0000* |
| 11/09/1999 | ELECTRIC - FINAL | RFREIDIN | Approved | IVRS - Inspection 0000* |
| 11/09/1999 | BUILDING - FINAL | RFREIDIN | Approved | IVRS - Inspection 0000* |
| 11/09/1999 | SHEET ROCK NAILING | RFREIDIN | Approved | NOT READY FOR INSPECTION |
| 11/09/1999 | SHEET ROCK NAILING | RFREIDIN | Approved | ADDTL COMMS - NOT READY - 1. CHECK HOT NEUTRAL REVISED AT DINING ROOM. 2. CHECK OUTLET SPACING. 3. DUCT WORK IS NOT INSTALLED PER PLAN OR CODE. 4. BEAM HAS NO BEARING AT BAY WINDOW. 5. CONDUIT ON ROOF. NO ROOF JACK. NOT SUPPORTED. 6. NEED CLEARANCE AT SERVICE PANEL. POINT OF ATTACHMENT. 7. 30 AMP BREAKER FOR 15 AMP CIRCUIT. #14 GAUGE WIRE. |