Permit: T99CM04092
Permit Details
Apply Date:
08/25/1999
Applicant:
ROGERS BILL
Description:
TI:RESTAURANT
Architects:
- SIU, WAYNE CHONG
Outstanding Inspections
Permit Status: Expired
Permit Number: T99CM04092
Permite Description: TI:RESTAURANT
Total Outstanding Inspections - 4
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
EXCAVATION/LAYOUT REBAR & ZON | N/A | Not Inspected | ||
SHEET ROCK NAILING | N/A | Not Inspected | ||
12/01/2015 | FIRE - FINAL | N/A | Denied | 1. Upgrade hood system to UL 300. 2. All exit signs need to be functioning with battery backup. 3. Need Occupant Load signs. 4. Remove drop bars on exit doors. 5. Remove dead bolts on exit doors with panic hardware. 6. Fire extinguishers needed throughout building. 7. Address numbers needed on exterior. |
12/21/1999 | BUILDING - FINAL | N/A | Correction Required | ADDTL COMMS - PROVIDE 15 ADDRESS NUMBERS VISIBLE FROM BENSON HIGHWAY. |
Completed Inspections
Permit Status: Expired
Permit Number: T99CM04092
Permit Description: TI:RESTAURANT
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/15/1999 | ELECTRIC - INTERMEDIATE | JORTA | Approved | ADDTL COMMS - WOMEN AND MENS TOILET ROUGH WALK AND CEILING APPROVED |
12/21/1999 | PLUMBING - FINAL | TVALENCI | Approved | IVRS - Inspection 0000* |
12/21/1999 | PLUMBING - FINAL | TVALENCI | Approved | ADDTL COMMS - C/L ON URINAL SHALL BE 6 ABOVE TOP IS URINAL NEED CORRECTIONAL FITTING AT SINKS @ LOUNEGE BAR-NOT READY NOT A COMPLETE INSPECTION |