Permit Details

Status:
Expired
Type:
COMMERCIAL OTHER
Apply Date:
03/16/1999
Applicant:
RECORD ENERGY CONCEPTS INC ,
Description:
REMODEL FOR AIR COND: INFILL OPENINGS AT ONE-HOUR CONSTRUCTION REPLACE DOORS AT ONE-HOUR WALLS W/ 20 MINUTE RATED ASSEMBLIES REFRAME ROOF AS SHOWN FOR SUPPORT OF EQUIPMENT
Contractors:
  • RECORD ENERGY CONCEPTS INC ,

Permit Reviews

Permit Number - T99CM01131
Permit Status: Expired
Permit Description: REMODEL FOR AIR COND: INFILL OPENINGS AT ONE-HOUR CONSTRUCTION REPLACE DOORS AT ONE-HOUR WALLS W/ 20 MINUTE RATED ASSEMBLIES REFRAME ROOF AS SHOWN FOR SUPPORT OF EQUIPMENT
Start Date Submittal Complete Date Status  
01/16/2001 REVISION 01/16/2001 COMPLETED Review Details
12/26/2000 REVISION 04/10/2001 COMPLETED Review Details

Outstanding Inspections

Permit Status: Expired
Permit Number: T99CM01131
Permite Description: REMODEL FOR AIR COND: INFILL OPENINGS AT ONE-HOUR CONSTRUCTION REPLACE DOORS AT ONE-HOUR WALLS W/ 20 MINUTE RATED ASSEMBLIES REFRAME ROOF AS SHOWN FOR SUPPORT OF EQUIPMENT
Total Outstanding Inspections - 8
Last Inspection Date Description Inspector Results Comments
MECHANICAL - INTERMEDIATE N/A Not Inspected
FIRE SPKLR - FINAL N/A Not Inspected
FIRE - FINAL N/A Not Inspected
01/09/2001 PLUMBING - FINAL N/A Not ready for Inspection IVRS - Inspection 0000*
04/18/2000 MECHANICAL - PROGRESS N/A Correction Required ADDTL COMMS - I.D. # NUMBERS, CONDENSERS AND SWITHCES. MATCH AND MARK AIR HANDLERS. BLOCK, CLAMP REFIG LINES AS NECESSARY, OUTSIDE AT CONDENSERS..
11/01/2000 PLUMBING - GAS PRESSURE TEST N/A Partial Approval PARTIAL ON GAS TEST NEED TO COMPLETE GAS LINE TO KITCHEN EQUIPTMENT AND CALL FOR MECH INSPECTION ON ROOF TOP UNIT/ CALL WHEN READY
12/05/2000 MECHANICAL - ABOVE CEILING N/A Partial Approval IVRS - Inspection 0000*
12/05/2000 MECHANICAL - FINAL N/A Partial Approval IVRS - Inspection 0000*

Completed Inspections

Permit Status: Expired
Permit Number: T99CM01131
Permit Description: REMODEL FOR AIR COND: INFILL OPENINGS AT ONE-HOUR CONSTRUCTION REPLACE DOORS AT ONE-HOUR WALLS W/ 20 MINUTE RATED ASSEMBLIES REFRAME ROOF AS SHOWN FOR SUPPORT OF EQUIPMENT
Total Completed Inspections - 3
Date Description Inspector Results Comments
12/29/2000 ELECTRIC - FINAL RHOLLAND Approved IVRS - Inspection 0000*
FILL ALL UNUSED OPENINGS
DOUBLE LUG AT SUPPLY FAN A AND #12 CONDUCTOR W/70 AMP FUSES
STRAP 2" SEAL TITE
01/05/2001 SHEET ROCK NAILING EMONAHAN Approved IVRS - Inspection 0000$
W/NOTE NAIL LATH AT BOTTOM SIDE OF BEAMS AT 6" O.C LINE THE REST OF THE LATH THEN OK TO PLASTER
01/10/2001 BUILDING - FINAL EMONAHAN Approved IVRS - Inspection 0000*