Status:
Expired
Type:
SINGLE FAMILY ADDITION
Address NEW:
5043 E HAWTHORNE ST
Apply Date:
11/05/1997
Applicant:
CHAVEZ MARIO S & ROSEMARIE C JT/
Description:
ADDITION:BEDROOM & BATHROOM
Contractors:
  • SILVER WEST INC ,

Outstanding Inspections

Permit Status: Expired
Permit Number: T97CM03572
Permite Description: ADDITION:BEDROOM & BATHROOM
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
PERMIT FINALED N/A Not Inspected
03/06/1998 ELECTRIC - TEMPORARY SERVICE N/A Correction Required ADDTL COMMS - 1. GIRD AT OLD SERV NOT VERIFIED, SO GRD TO BE RUN TO NEW SERV WITH SUB/ PANEL FEEDERS. 2. 70 AMP 2 POLE BREAKE 65 AMPS MAX RETING FOR #6 CO.
05/29/1998 PLUMBING - INTERMEDIATE N/A Partial Approval PARTIAL APPROVAL
08/04/1998 BUILDING - FINAL N/A Partial Approval PARTIAL APPROVAL
08/04/1998 ELECTRIC - FINAL N/A Correction Required ADDTL COMMS - NO POWER TO THREE OUTLTS EXTERIOR GFCI AND WATER HEATER ROOM.

Completed Inspections

Permit Status: Expired
Permit Number: T97CM03572
Permit Description: ADDITION:BEDROOM & BATHROOM
Total Completed Inspections - 2
Date Description Inspector Results Comments
02/24/1998 BUILDING PRE-SLAB RFREIDIN Approved ADDTL COMMS - 1. H2O LINE GAW BELOW SLAB TO BE REROUTED NOT TO BE UNDER SLAB OLD GROUND AT EXISTING SERV. CLAMP EXISTING ELECTRODE CONDUCTOR A LEGAL GRDINC CONDUCTOR. THIS SERV, IS UNDER AT THIS TIME.
03/17/1998 ELECTRIC - SERVICE RELOCATION RFREIDIN Approved ADDTL COMMS - TEP WILL INSP YOUR TRENCH - YOU WILL NEED A WATER BOND BEFORE FINAL - WILL CHECK AT INTERMEDIATE. NO PERMIT OR LAST INSP RESULTS LEFT IN PLAN TUBE - #6 IS GOOD FOR A 60 AMP LOAD ALL OTHER CIRCUITS TO GO TO NEW PANEL

Documents