Permit: T97CM00184
Permit Details
Status:
Expired
Type:
SINGLE FAMILY ADDITION
Address:
1448 S AVENIDA SIRIO
Address NEW:
1448 S AVENIDA SIRIO
Apply Date:
03/10/1997
Applicant:
NOPERI CLAUDIO & REGINA JT/RS
Description:
ADDITION AND REMODEL EXST RESIDENCE
Outstanding Inspections
Permit Status: Expired
Permit Number: T97CM00184
Permite Description: ADDITION AND REMODEL EXST RESIDENCE
Total Outstanding Inspections - 16
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| SHEET ROCK NAILING | N/A | Not Inspected | ||
| ELECTRIC - UFER | N/A | Not Inspected | ||
| ELECTRIC - CABLE DROP | N/A | Not Inspected | ||
| ELECTRIC - TEMPORARY SERVICE | N/A | Not Inspected | ||
| PLUMBING - ROUGH, SOIL | N/A | Not Inspected | ||
| PLUMBING - INTERMEDIATE | N/A | Not Inspected | ||
| PLUMBING - YARD WTR LINE/TEST | N/A | Not Inspected | ||
| PLUMBING - SEWER HCS CONNECT | N/A | Not Inspected | ||
| MECHANICAL - INTERMEDIATE | N/A | Not Inspected | ||
| PERMIT FINALED | N/A | Not Inspected | ||
| 02/02/1999 | BUILDING - FINAL | N/A | Correction Required | ADDTL COMMS - 1. RAISE H2O HEATER FLUE 1 ABOVE COOLER. 2. FIREPLACE IS GOING TO BE A LOG LITER, OR GAS LOG PLEASE INSTALL. 3. FINISH KITCHEN, CABINETS AND PLUMBING, RANGE PAN. 4. BATHROOM PLUMBING LIGHTING FIXTURES NOT COMPLETE. 5. EXT OUTLETS NOT INSTALLED. 6. NEED A STOOP AT REAR DOOR 3X3 CAN BE BRICK 4 STEP. 7. ELECT SERVICE HAS NOT BEEN CONNECTED BY T.E.P WAS IT INSPECTED? H2O BOND? 8. COOLER OUTLET TRAPPED UP UNABLE TO INSPECT. 9. NEED CONDENSATE LINE FOR A.C. 10. SUPPORT/SECURE GAS LINE. |
| 02/02/1999 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection 0999* |
| 02/02/1999 | PLUMBING - FINAL | N/A | Denied | IVRS - Inspection 0999* |
| 02/02/1999 | MECHANICAL - FINAL | N/A | Denied | IVRS - Inspection 0999* |
| 07/12/1999 | ELECTRIC - SERVICE UPGRADE | N/A | Correction Required | ADDTL COMMS - YOU NEED TO EXPOSE GROUNDING AND H20 BOND. 2 GRD RODS REQUIRED PLUS WATER BOND. |
| 11/20/1997 | ELECTRIC - INTERMEDIATE | N/A | Correction Required | ADDTL COMMS - 1. PLEASE LABEL CIRCUITS IN PANEL 60 TWO POLE BREAKER NOT ON PANEL SCHEDULE OR LOAD CALC 2. DRYER VENT STRAP OUTSIDE REMOVE SCREW FROM INSIDE OF VENT. |
Completed Inspections
Permit Status: Expired
Permit Number: T97CM00184
Permit Description: ADDITION AND REMODEL EXST RESIDENCE
Total Completed Inspections - 4
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/1997 | ROOF NAILING | HLEYVA | Approved | ADDTL COMMS - NOTE - YOU ARE REPLACING BEDROOM WINDOWS THAT DO NOT MEET MINIMUM REQUIREMENTS FOR OPENING & LIGHT |
| 11/20/1997 | PLUMBING - GAS PRESSURE TEST | RFREIDIN | Approved | NOT READY FOR INSPECTION |
| 11/20/1997 | PLUMBING - GAS PRESSURE TEST | RFREIDIN | Approved | ADDTL COMMS - 1. GAS LINE NOT ALLOWED UNDER ROOF STRUCTURE AT REAR DOOR. 2. FURANCE NOTHING ON PLAN SHOWING ANY CHANGES OLD FURANCE ROOM HAS NO PLENUM, VERIFY RELIEF/COMB DUCTS TO OUTSIDE VENTING. 3. 2 PIPE IN KITCHEN FLOOR? 4. MISSING FIRE PLACE HEARTH SAFTEY STRIP. 5.DUCT WORK TO BE INSULATED 1 MIN VAPOR BARRIER FOR HEATING DUCT. 6. BLOCK ALL MECH. VENTS 3 SIDES. |
| 08/27/1998 | STUCCO MESH | RFREIDIN | Approved | ADDTL COMMS - YOU NEED A PLASTER GROUND AT FREEZE BOARDS COVERED PORCH REAR TOP OF WALL |