Permit: T22OT00683
Permit Details
Apply Date:
09/20/2022
Applicant:
Kimberly Euers
Description:
1 illum wall sign / Safeway
Permit Reviews
Permit Number - T22OT00683
Permit Status: Complete
Permit Description: 1 illum wall sign / Safeway
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
02/03/2023 | PERMANENT SIGN REVIEW v.2 | 02/07/2023 | APPROVED |
11/04/2022 | PERMANENT SIGN REVIEW v.1 | 12/06/2022 | REQUIRES RESUBMIT |
Outstanding Inspections
Permit Status: Complete
Permit Number: T22OT00683
Permite Description: 1 illum wall sign / Safeway
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/23/2022 | COT - ENGR - Signage Final | N/A | Partial Pass | {Activity date: 09/23/2022; Status: Partial Approval; Inspector: hthral; Comment: Entered by HTHRALL1 - RE: wall sign review For: Safeway AT: 10380 E Broadway Bl Sign permit: T22OT00683 Reviewer: H.Thrall Date: 09/23/22 Codes: Unified Development Code 7A, Sign Standards, National Electrical Code (NEC), Tucson Pima County Outdoor Lighting Code and International Building Code (IBC) 2018 Permit Status: Partial apprval - please provide following notes for permit record: 1. UDC. Amend calculation for total allowed building sign area to a cap of 250 sqft per scenic route / scenic sign district. Take out the panels for monument sign listing, as they are now separately calced on scenic routes from building signs and existing. (Thanks for the sign area chart breakdown, very helpful!) 2. Property management signature was not on the LL approval doc, ok to send an email from them to release permit. 3. NEC 600 / OLC: Ch 4 & 5 A. provide note "signs shall shut off by midnight curfew via timer" B. provide note with location of timer (by panel or is it corporate timer?) C. provide note clarifying location of electrical panel in building D. provide note that all dedicated sign circuits shall be labeled E. remove note referring to 200 Nits brightness for this plan, applies to digital signs when they have to dim at sunset to sunrise 4. IBC A. side view calls out letters versus cabinet proposed - is cabinet same depth at 5" B. please check mounts to wall since it's a cabinet (i.e. diameter / length) and note typical number needed Thank you for really clear plan set - appreciated for the review. Please send updated plan docs to Heather.Thrall@tucsonaz.gov} |
Completed Inspections
Permit Status: Complete
Permit Number: T22OT00683
Permit Description: 1 illum wall sign / Safeway
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/15/2023 | COT - SIGN - Self Certification Inspection | Passed |