Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T22CM05014
Permit Details
Apply Date:
07/02/2022
Applicant:
ramon polanco
Description:
SFR BRIO1432 T20-M0058
Permit Reviews
Permit Number - T22CM05014
Permit Status: Complete
Permit Description: SFR BRIO1432 T20-M0058
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
07/02/2022 | OTHER | 08/05/2022 | COMPLETED |
02/07/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 02/09/2024 | APPROVED |
02/27/2024 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 02/28/2024 | APPROVED |
Conditions
Permit Number - T22CM05014
Permit Status: Complete
Permit Description: SFR BRIO1432 T20-M0058
Date | Description | Comments |
---|---|---|
07/02/2022 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. | |
07/02/2022 | SPECIAL INSPECTION FORMS AND REPORTS REQUIRED PRIOR TO ISSUANCE OF A CERTIFICATE OF OCCUPANCY. | |
07/02/2022 | SPECIAL INSPECTION FOR EXPANSION ANCHORS IS REQUIRED. | |
08/05/2022 | Prior to permit issuance a General Contractor Letter (GCL) is required | |
02/26/2024 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. | |
02/26/2024 | Water Meter Size | |
02/26/2024 | SPECIAL INSPECTION FOR POST TENSION SLAB IS REQUIRED. | |
02/26/2024 | Truss/Joist Design plans must be submitted and approved prior to intermediate inspections if residential building or finaling the permit if commercial building. |
Outstanding Inspections
Permit Status: Complete
Permit Number: T22CM05014
Permite Description: SFR BRIO1432 T20-M0058
Total Outstanding Inspections - 3
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2024 | COT - RSEL - Construction Power | N/A | Not Applicable | |
02/01/2024 | COT - RSBU - Sustainability | N/A | Not Applicable | |
02/15/2024 | RSBU - Building Final | N/A | Re-inspection required (with fee) |
Completed Inspections
Permit Status: Complete
Permit Number: T22CM05014
Permit Description: SFR BRIO1432 T20-M0058
Total Completed Inspections - 20