Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
Fire Construction Permit
Address:
3655 E GRANT RD
Address NEW:
3655 E GRANT RD
Apply Date:
06/03/2021
Applicant:
Description:
Automatic Fire Extingshing Sys - Install a new wet-pipe sprinkler system in an existing 33,460 sq.ft. two-story; Commercial Fire Sprinkler Systems - Underground Fire Line Supply; Additional Plan Reviews: 1

Completed Inspections

Permit Status: Expired
Permit Number: T21FC00441
Permit Description: Automatic Fire Extingshing Sys - Install a new wet-pipe sprinkler system in an existing 33,460 sq.ft. two-story; Commercial Fire Sprinkler Systems - Underground Fire Line Supply; Additional Plan Reviews: 1
Total Completed Inspections - 4
Date Description Inspector Results Comments
03/17/2022 COT - FCON - Underground Flush Passed {Activity date: 03/17/2022; Status: Approved; Inspector: jfordney; Comment: Entered by JFORDNE1 - }
03/21/2022 COT - FCON - Sprinkler - Final Passed {Activity date: 03/21/2022; Status: Approved; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - } ; {Activity date: 03/17/2022; Status: Denied; Inspector: jfordney; Comment: Entered by JFORDNE1 - Need "as builts" (stairwells and soffit)
Cieling tiles throughout
Missing head in FACP room}
01/11/2022 FCON – OH Piping & Hydro Passed {Activity date: 01/11/2022; Status: Approved; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - 210psi} ; {Activity date: 09/23/2021; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Ok to hard lid on 1st and 2nd floor. 210psi.}
07/22/2021 COT - FCON - Underground Pressure Passed {Activity date: 07/22/2021; Status: Approved; Inspector: jfordney; Comment: Entered by JFORDNE1 - 230 psi}