Permit: T21CM07679
Permit Details
Apply Date:
09/24/2021
Applicant:
Ryan Wilt
Description:
New Community Building, covered patios, detached ramada, site lighting & pickle ball court
Permit Reviews
Permit Number - T21CM07679
Permit Status: Complete
Permit Description: New Community Building, covered patios, detached ramada, site lighting & pickle ball court
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
09/24/2021 | COMMERCIAL - NEW | 12/14/2021 | COMPLETED |
09/29/2022 | RESUBMITTAL | 10/13/2022 | COMPLETED |
10/15/2022 | RESUBMITTAL | 10/15/2022 | ACTIVE |
11/20/2023 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 11/21/2023 | APPROVED |
08/23/2023 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 08/28/2023 | APPROVED |
11/01/2023 | BUILDING DEFERRED SUBMITTAL REVIEW v.1 | 11/02/2023 | APPROVED |
12/14/2022 | COMMERCIAL REVIEW - FULL v.1 | 01/12/2023 | APPROVED |
10/28/2022 | COMMERCIAL REVIEW - FULL v.1 | 11/01/2022 | REQUIRES RESUBMIT |
11/15/2022 | COMMERCIAL REVIEW - FULL v.2 | 12/14/2022 | REQUIRES RESUBMIT |
Conditions
Permit Number - T21CM07679
Permit Status: Complete
Permit Description: New Community Building, covered patios, detached ramada, site lighting & pickle ball court
Date | Description | Comments |
---|---|---|
11/15/2022 | AIR BALANCING/COMMISSIONING REPORT IS REQUIRED. | |
10/04/2021 | ROOF TRUSSES MUST BE APPROVED PRIOR TO FRAMING INSPECTION (P2I) | |
10/04/2021 | SPECIAL INSPECTION FOR CONCRETE IS REQUIRED.. | |
10/04/2021 | SPECIAL INSPECTION FOR REINFORCING STEEL AND/OR PRE-STRESSING TENDONS IS REQUIRED. | |
10/04/2021 | SPECIAL INSPECTION FOR STRUCTURAL WELDING IS REQUIRED. | |
10/04/2021 | SPECIAL INSPECTION FOR HIGH STRENGTH BOLTING IS REQUIRED. | |
10/04/2021 | SPECIAL INSPECTION FOR STRUCTURAL MASONRY IS REQUIRED. | |
10/04/2021 | SPECIAL INSPECTION FOR SITE PREPARATION IS REQUIRED. | |
10/04/2021 | SPECIAL INSPECTION FOR FIELD WELDING IS REQUIRED. | |
10/04/2021 | SPECIAL INSPECTION FOR EPOXY ANCHORS IS REQUIRED. | |
10/11/2022 | SPECIAL INSPECTION REQUIRED FOR OUTDOOR LIGHTING | |
01/12/2023 | Contractor with active Arizona Contractor's License for specified scope of work required prior to issuance of permit. | |
11/15/2022 | WATER STERILIZATION REPORT IS REQUIRED. |
Outstanding Inspections
Permit Status: Complete
Permit Number: T21CM07679
Permite Description: New Community Building, covered patios, detached ramada, site lighting & pickle ball court
Total Outstanding Inspections - 5
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/14/2023 | COT - LCEL - Electrical Final | N/A | Re-inspection required | 8/14/23: city approved plans are required on site. No record of any framing or grout inspections. Blank cover missing in electric panel. Secure NMC cable to wall at water heater. All exterior electric outlets are required to be WR. Both ADA sinks exceed 34", men's toilet exceeds 18" off wall, wrap plumbing under sinks, incorrect restroom signage, toilet flush valve not on the open side in men's restroom, grab bars missing in shower, seat missing in shower, coat hooks exceed max 48" off floor.Support NMC cable in court yard off concrete |
08/14/2023 | COT - HCBU - Building Final | N/A | Re-inspection required | 8/14/23: city approved plans are required on site. No record of any framing or grout inspections. Blank cover missing in electric panel. Secure NMC cable to wall at water heater. All exterior electric outlets are required to be WR. Both ADA sinks exceed 34", men's toilet exceeds 18" off wall, wrap plumbing under sinks, incorrect restroom signage, toilet flush valve not on the open side in men's restroom, grab bars missing in shower, seat missing in shower, coat hooks exceed max 48" off floor.Support NMC cable in court yard off concrete |
08/14/2023 | COT - HCEL - Electrical Final | N/A | Re-inspection required | 8/14/23: city approved plans are required on site. No record of any framing or grout inspections. Blank cover missing in electric panel. Secure NMC cable to wall at water heater. All exterior electric outlets are required to be WR. Both ADA sinks exceed 34", men's toilet exceeds 18" off wall, wrap plumbing under sinks, incorrect restroom signage, toilet flush valve not on the open side in men's restroom, grab bars missing in shower, seat missing in shower, coat hooks exceed max 48" off floor.Support NMC cable in court yard off concrete |
08/14/2023 | COT - HCME - Mechanical Final | N/A | Re-inspection required | 8/14/23: city approved plans are required on site. No record of any framing or grout inspections. Blank cover missing in electric panel. Secure NMC cable to wall at water heater. All exterior electric outlets are required to be WR. Both ADA sinks exceed 34", men's toilet exceeds 18" off wall, wrap plumbing under sinks, incorrect restroom signage, toilet flush valve not on the open side in men's restroom, grab bars missing in shower, seat missing in shower, coat hooks exceed max 48" off floor.Support NMC cable in court yard off concrete |
08/14/2023 | COT - HCPL - Plumbing Final | N/A | Re-inspection required | 8/14/23: city approved plans are required on site. No record of any framing or grout inspections. Blank cover missing in electric panel. Secure NMC cable to wall at water heater. All exterior electric outlets are required to be WR. Both ADA sinks exceed 34", men's toilet exceeds 18" off wall, wrap plumbing under sinks, incorrect restroom signage, toilet flush valve not on the open side in men's restroom, grab bars missing in shower, seat missing in shower, coat hooks exceed max 48" off floor.Support NMC cable in court yard off concrete |
Completed Inspections
Permit Status: Complete
Permit Number: T21CM07679
Permit Description: New Community Building, covered patios, detached ramada, site lighting & pickle ball court
Total Completed Inspections - 26
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/01/2023 | COT - HCPL - Sewer | Passed | ||
03/27/2023 | COT - LCEL - Electrical Underground | Passed | ||
03/27/2023 | COT - LCEL - Grounding/Bonding | Passed | ||
03/29/2023 | COT - HCPL - Rough Soil | Passed | ||
03/29/2023 | COT - HCPL - Yard Water Line | Passed | ||
03/29/2023 | COT - LCPL - Plumbing Progress | Passed | ||
04/05/2023 | COT - LCBU - Excavation/Rebar/Zoning | Passed | ||
04/05/2023 | COT - LCBU - Preslab | Passed | ||
04/13/2023 | COT - HCEL - Electrical Underground | Passed | ||
04/13/2023 | COT - HCEL - Grounding/Bonding | Passed | ||
06/05/2023 | COT - LCEL - Electrical Above Ceiling | Passed | ||
06/05/2023 | COT - LCEL - Electrical Intermediate | Passed | ||
06/05/2023 | COT - HCPL - Plumbing Intermediate | Passed | ||
06/05/2023 | COT - HCME - Mechanical Intermediate | Passed | ||
06/05/2023 | BULD - Electrical Clearance | Passed | ||
08/14/2023 | COT - LCEL - Electrical Progress | Passed | ||
08/14/2023 | COT - LCEL - Outdoor Lighting | Passed | ||
08/14/2023 | COT - FCON - Alarm - Final | Passed | no alarms | |
08/14/2023 | COT - FCON - Fire - Final | Passed | ||
09/14/2023 | COT - FCON - Sprinkler - Final | Passed | there are no sprinklers in this area. | |
09/05/2023 | ENGR Engineering Final | Passed | ||
09/05/2023 | COT - LCEL - Electrical Final | Passed | 8/14/23: city approved plans are required on site. No record of any framing or grout inspections. Blank cover missing in electric panel. Secure NMC cable to wall at water heater. All exterior electric outlets are required to be WR. Both ADA sinks exceed 34", men's toilet exceeds 18" off wall, wrap plumbing under sinks, incorrect restroom signage, toilet flush valve not on the open side in men's restroom, grab bars missing in shower, seat missing in shower, coat hooks exceed max 48" off floor.Support NMC cable in court yard off concrete 9/5/23: all corrections made |
|
09/05/2023 | COT - HCBU - Building Final | Passed | 8/14/23: city approved plans are required on site. No record of any framing or grout inspections. Blank cover missing in electric panel. Secure NMC cable to wall at water heater. All exterior electric outlets are required to be WR. Both ADA sinks exceed 34", men's toilet exceeds 18" off wall, wrap plumbing under sinks, incorrect restroom signage, toilet flush valve not on the open side in men's restroom, grab bars missing in shower, seat missing in shower, coat hooks exceed max 48" off floor.Support NMC cable in court yard off concrete 9/5/23: all corrections made |
|
09/05/2023 | COT - HCEL - Electrical Final | Passed | 8/14/23: city approved plans are required on site. No record of any framing or grout inspections. Blank cover missing in electric panel. Secure NMC cable to wall at water heater. All exterior electric outlets are required to be WR. Both ADA sinks exceed 34", men's toilet exceeds 18" off wall, wrap plumbing under sinks, incorrect restroom signage, toilet flush valve not on the open side in men's restroom, grab bars missing in shower, seat missing in shower, coat hooks exceed max 48" off floor.Support NMC cable in court yard off concrete 9/5/23: all corrections made |
|
09/05/2023 | COT - HCME - Mechanical Final | Passed | 8/14/23: city approved plans are required on site. No record of any framing or grout inspections. Blank cover missing in electric panel. Secure NMC cable to wall at water heater. All exterior electric outlets are required to be WR. Both ADA sinks exceed 34", men's toilet exceeds 18" off wall, wrap plumbing under sinks, incorrect restroom signage, toilet flush valve not on the open side in men's restroom, grab bars missing in shower, seat missing in shower, coat hooks exceed max 48" off floor.Support NMC cable in court yard off concrete 9/5/23: all corrections made |
|
09/05/2023 | COT - HCPL - Plumbing Final | Passed | 8/14/23: city approved plans are required on site. No record of any framing or grout inspections. Blank cover missing in electric panel. Secure NMC cable to wall at water heater. All exterior electric outlets are required to be WR. Both ADA sinks exceed 34", men's toilet exceeds 18" off wall, wrap plumbing under sinks, incorrect restroom signage, toilet flush valve not on the open side in men's restroom, grab bars missing in shower, seat missing in shower, coat hooks exceed max 48" off floor.Support NMC cable in court yard off concrete 9/5/23: all corrections made |