Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
Flammable & Combustible Liquid
Address:
6220 S TUCSON BL
Apply Date:
10/30/2020
Applicant:
CAID INDUSTRIES INC , T A
Description:
1000 gal. diesel tank, above ground tank and associated paving.
Contractors:
  • CAID INDUSTRIES INC , T A

Completed Inspections

Permit Status: Final
Permit Number: T20FC00748
Permit Description: 1000 gal. diesel tank, above ground tank and associated paving.
Total Completed Inspections - 1
Date Description Inspector Results Comments
01/13/2021 FUEL TANK FINAL 791-4502 jhinric Approved bollards placed, e stop tested and working, e stop labeled, tank labled, tank is UL 142(double walled), vents placed appropriatley, tank fill gauge installed, breakaway installed.