Permit: T20FC00685
Permit Details
Apply Date:
10/15/2020
Applicant:
HSL CONSTRUCTION SVCS LLC
Description:
Bldg 8 - Encantada Saguaro Trails underground fire service line
Contractors:
- HSL CONSTRUCTION SVCS LLC
Completed Inspections
Permit Status: Final
Permit Number: T20FC00685
Permit Description: Bldg 8 - Encantada Saguaro Trails underground fire service line
Total Completed Inspections - 2
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2021 | FIRE SPKLR - UG, PIPING, HYDRO | jfordney | Approved | After being under pressure for 3 hours gauge read 195 psi. after close examination it was detemined there was a small leak coming from the ball valve that capped the run, NOT the fire line. |
09/01/2021 | FIRE SPKLR - UG PIPING FLUSH | jfordney | Approved |