Permit: T20CM08944
Permit Details
Apply Date:
12/21/2020
Applicant:
sunset holdings AZ
Description:
electrical re connect inspection
Contractors:
Completed Inspections
Permit Status: Final
Permit Number: T20CM08944
Permit Description: electrical re connect inspection
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/31/2020 | ELECTRIC - RECONNECT | RBOOHER | Approved | DE...E3601.6.1: Please add address marking on service disconnect to distinguish from others...E3404.6 please plug open knockouts.. E3607.5 main bonding jumper partially missing needs re established.. |
| 01/06/2021 | TEP CLEARANCE - PM | TGAUSP | Approved | CODE RECN |
| 01/06/2021 | ELECTRIC - FINAL | TGAUSP | Approved | APPROVED |