Permit: T20CM05035
Permit Details
Status:
Expired
Type:
Residential Building - One or Two Family
Address:
2521 E ELM ST
Address NEW:
2521 E ELM ST
Apply Date:
08/04/2020
Applicant:
RICK BRIGHT
Description:
PC- PV PANELS
Permit Reviews
Permit Number - T20CM05035
Permit Status: Expired
Permit Description: PC- PV PANELS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/20/2020 | RESIDENTIAL - BLDG/ZONING/ENGINE/NPPO | 08/11/2020 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T20CM05035
Permit Status: Expired
Permit Description: PC- PV PANELS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 08/04/2020 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Conditions
Permit Number - T20CM05035
Permit Status: Expired
Permit Description: PC- PV PANELS
| Date | Description | Comments |
|---|---|---|
| 08/04/2020 | THE INSTALLATION SHALL COMPLY WITH ALL APPLICABLE REQUIREMENTS OF SECTION 605.11.1 THROUGH 605.11.4 OF THE 2012 EDITION OF THE INTERNATIONAL FIRE CODE, THE INTERNATIONAL BUILDING CODE AND NFPA 70. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T20CM05035
Permite Description: PC- PV PANELS
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2022 | COT - RSEL - Electrical Underground | N/A | Canceled | Inspection Canceled |
| 11/07/2022 | RSBU - Building Final | N/A | Canceled | Inspection Canceled |
Completed Inspections
Permit Status: Expired
Permit Number: T20CM05035
Permit Description: PC- PV PANELS
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/23/2021 | COT - RSEL - Service Upgrade | Passed | {Activity date: 07/23/2021; Status: Approved; Inspector: DQUINN; Comment: Entered by VLEON1 - } ; {Activity date: 05/17/2021; Status: Not ready for Inspection; Inspector: DQUINN; Comment: Entered by VLEON1 - 7:20 No message with contact phone # left, and no # on pplication. Call to arrange virtual inspection. Dan 5204904765. 3pm No response to this message. Please recall and be sure to leave a message with a contact phone number number, to perform a virtual inspection. 2065 nr} |
|
| 08/31/2021 | PDSD Building Division - TEP PMÂ Clearance | Passed | {Activity date: 08/31/2021; Status: Approved; Inspector: RELEFANTE; Comment: Entered by NGARCIA3 - CODE DGC} ; {Activity date: 07/23/2021; Status: Approved; Inspector: DQUINN; Comment: Entered by VLEON1 - CODE INCR} | |
| 08/31/2021 | COT - RSEL - Electrical Final | Passed | {Activity date: 08/31/2021; Status: Approved; Inspector: RELEFANTE; Comment: Entered by NGARCIA3 - AP Clear DGC} ; {Activity date: 08/18/2021; Status: Not ready for Inspection; Inspector: DQUINN; Comment: Entered by RSALDAT1 - nr Need labels and ground connections in panels. } ; {Activity date: 08/16/2021; Status: Denied; Inspector: RELEFANTE; Comment: Entered by RSALDAT1 - DE Plans call for 200 amp main breaker, they installed a 100 and scribbled out the 200 on the plans and wrote 100. Plans also call for 15&45 breaker in panel they have neither installed. And panel not labeled} ; {Activity date: 07/23/2021; Status: Not ready for Inspection; Inspector: DQUINN; Comment: Entered by VLEON1 - House panel for solar on multi unit property, and other common circuitry ok. Clear incr for new house panel. } |