Permit Details

Status:
Final
Type:
CO2 Systms -Bvrge Dspnsng Apps
Address:
300 W WETMORE RD
Address NEW:
300 W WETMORE RD
Apply Date:
06/13/2019
Applicant:
GLOBAL SYSTEMS UNITED
Description:
BULK CO2 SYSTEM WITH DETECTION

Completed Inspections

Permit Status: Final
Permit Number: T19FO00443
Permit Description: BULK CO2 SYSTEM WITH DETECTION
Total Completed Inspections - 2
Date Description Inspector Results Comments
09/18/2019 FIRE INSP - OPERATIONAL PERMIT jvincent Approved
09/18/2019 FIRE INSP - OPERATIONAL PERMIT jvincent Approved 1) Label/lock circuit breaker
2) Mount 704 diamond on back door.
3) Signals to central station are not correct. Power loss and CO2 high are both labeled as "carbon monoxide alarms."
4) Reinspection fee added to permit. Shall be paid prior to next inspection. Pretest systems and verify all signals prior to final inspections.