Permit: T19FC00824
Permit Details
Apply Date:
10/07/2019
Applicant:
Description:
Fire Alarm & Detection Systems - Replace FACP and add DAC (dual path Cell/IP; Fire Alarm Systems - Devices Modified: 2; Fire Alarm Systems - Monitoring Modification
Outstanding Inspections
Permit Status: Expired
Permit Number: T19FC00824
Permite Description: Fire Alarm & Detection Systems - Replace FACP and add DAC (dual path Cell/IP; Fire Alarm Systems - Devices Modified: 2; Fire Alarm Systems - Monitoring Modification
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/01/2019 | COT - FCON - Alarm - Final | N/A | Re-inspection required | {Activity date: 11/01/2019; Status: Denied; Inspector: jvincent; Comment: Entered by JVINCEN1 - -Did not test. -Requires one pull station in an approved location. -Requires smoke above the FACP. -Submit revision for review.} |