Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T19FC00708
Permit Details
Status:
Final
Type:
Flammable & Combustible Liquid
Address:
6280 E BROADWAY BL
Address NEW:
6280 E BROADWAY BL
Apply Date:
09/05/2019
Applicant:
EATON SALES AND SERVICES L L C
Description:
Install 2 new UGST & new double wall pipe & disp sumps
Contractors:
- EATON SALES AND SERVICES L L C
Completed Inspections
Permit Status: Final
Permit Number: T19FC00708
Permit Description: Install 2 new UGST & new double wall pipe & disp sumps
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/19/2020 | FUEL PIPING INSP. & PRESS TEST | jhinric | Approved | All lines passed pressure test and soap and water test. UDC passed hydrostatic test. Tanks passed pressure test. |
| 02/19/2020 | FUEL TANK TIGHTNESS AND HOLE | jhinric | Approved | Tanks arrived under vacuum pressure and maintained pressure throughout shipping process. Tanks placed correctly. |
| 03/04/2020 | FUEL TANK FINAL 791-4502 | jhinric | Approved | dispensers secure, shear valves secure, estop tested and working, fire extinguishers present, spill buckets tested and passed, monitor certification and tank testing passed. |