Permit: T19FC00499
Permit Details
Status:
Expired
Type:
Fire Construction Permit
Address:
600 S COUNTRY CLUB RD
Address NEW:
600 S COUNTRY CLUB RD
Apply Date:
06/27/2019
Applicant:
Description:
Fire Alarm & Detection Systems - Install Security System & Sprinkler Monitoring System; Fire Alarm Systems - Monitor Only; Fire Alarm Systems - Monitoring Modification; Additional Plan Reviews: 1
Outstanding Inspections
Permit Status: Expired
Permit Number: T19FC00499
Permite Description: Fire Alarm & Detection Systems - Install Security System & Sprinkler Monitoring System; Fire Alarm Systems - Monitor Only; Fire Alarm Systems - Monitoring Modification; Additional Plan Reviews: 1
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2019 | COT - FCON - Alarm - Final | N/A | Partial Pass | {Activity date: 08/23/2019; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - Need to add the dedicated function sign on the FACP Need RED lockout and disconnecting means labeled in panels Program and reverify the mag locks on the front doors} |