Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
Flammable & Combustible Liquid
Address NEW:
5561 E SPEEDWAY BL
Apply Date:
05/15/2019
Applicant:
E P A BUSINESS SOLUTIONS INC
Description:
INSTALL (2) 12,000 GAL UNDERGROUND FUEL STORAGE TANK, (6) DISPENSER CONTAINMONT SUMPS AND DBL WALL PRODUCT PIPING.
Contractors:
  • E P A BUSINESS SOLUTIONS INC

Completed Inspections

Permit Status: Final
Permit Number: T19FC00370
Permit Description: INSTALL (2) 12,000 GAL UNDERGROUND FUEL STORAGE TANK, (6) DISPENSER CONTAINMONT SUMPS AND DBL WALL PRODUCT PIPING.
Total Completed Inspections - 3
Date Description Inspector Results Comments
07/29/2019 FUEL PIPING INSP. & PRESS TEST jhinric Approved piping passed 1 hr pressure test and soap and water test, UDC's passed 1 hr hydrostatic test.
08/08/2019 FUEL TANK TIGHTNESS AND HOLE jhinric Approved vacuum pressure test passed. Tanks set in pit appropriately
08/26/2019 FUEL TANK FINAL 791-4502 jhinric Approved estop passed, shear valve and dispensers secure. Still need warning labels and shorter dispenser hoses.

Documents

File Name Document Type  
001_SHEET 1.TIF FIRE PLANS VIEW
002_SHEET 2.TIF FIRE PLANS VIEW
003_SHEET 1 OF 2.TIF FIRE PLANS VIEW
004_SHEET 2 OF 2.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW