Permit Details

Status:
Expired
Type:
Fire Construction Permit
Apply Date:
04/30/2019
Applicant:
Description:
Fire Alarm & Detection Systems - Burglar ALarm Take Over - Sprinler Tamper/Flow found to be on non-approved Panel - Swapping Existing nurglar Panel for New DMP XR150 Burglar/Fire Panel & Monitoring Testing 100% of Zones. Cell Primary w/Network Back-up; Fire Alarm Systems - Devices Modified: 1

Outstanding Inspections

Permit Status: Expired
Permit Number: T19FC00325
Permite Description: Fire Alarm & Detection Systems - Burglar ALarm Take Over - Sprinler Tamper/Flow found to be on non-approved Panel - Swapping Existing nurglar Panel for New DMP XR150 Burglar/Fire Panel & Monitoring Testing 100% of Zones. Cell Primary w/Network Back-up; Fire Alarm Systems - Devices Modified: 1
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
05/30/2019 COT - FCON - Alarm - Final N/A Partial Pass {Activity date: 05/30/2019; Status: Partial Approval; Inspector: jvincent; Comment: Entered by JVINCEN1 - -add smoke above
-add pull station in riser room
-submit plans
-add lockout to breaker & label}

Documents

File Name Document Type  
None DOCUMENTS VIEW