Fire Construction Permit
Apply Date:
04/01/2019
Applicant:
Description:
Fire Alarm & Detection Systems - Fire Alarm Monitoring of Flow & Tamper; Fire Alarm Systems - New Sq Ft: 7501; Fire Alarm Systems - # New Stories: 1

Outstanding Inspections

Permit Status: Expired
Permit Number: T19FC00227
Permite Description: Fire Alarm & Detection Systems - Fire Alarm Monitoring of Flow & Tamper; Fire Alarm Systems - New Sq Ft: 7501; Fire Alarm Systems - # New Stories: 1
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
07/03/2019 COT - FCON - Alarm - Final N/A Partial Pass {Activity date: 07/03/2019; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - Need RED FA lock out and electrical panel id
Transformers need to be in a locked enclosure
Need cellular dialer to annunciate power loss at the FACP
T19FC00227}