Permit: T19CM01809
Permit Details
Status:
Expired
Type:
COMMERCIAL ALTERATION
Address:
7545 S HOUGHTON RD #185
Address NEW:
7545 S HOUGHTON RD #185
Apply Date:
03/13/2019
Applicant:
N/A
Description:
TI: RESTAURANT
Architects:
- FIELDS, JAMES SLOAN
Contractors:
- A D REMODELING AND CONSTRUCTION INC
Permit Reviews
Permit Number - T19CM01809
Permit Status: Expired
Permit Description: TI: RESTAURANT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 03/13/2019 | COMMERCIAL - TI | 03/15/2019 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T19CM01809
Permit Status: Expired
Permit Description: TI: RESTAURANT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 03/13/2019 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T19CM01809
Permite Description: TI: RESTAURANT
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2019 | FIRE SPKLR - FINAL | N/A | Partial Approval | Replace painted heads -hallway closet -kitchen closet |
| 05/01/2019 | FIRE - KITCHEN EXH HOOD FINAL | N/A | Partial Approval | -need to interconnect to FACP -will need to verify once connection is made -will need to verify signals with central station |
Completed Inspections
Permit Status: Expired
Permit Number: T19CM01809
Permit Description: TI: RESTAURANT
Total Completed Inspections - 9
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2019 | PLUMBING - PRE SLAB | DQUINN | Approved | |
| 04/04/2019 | PLUMBING - ROUGH, SOIL | DQUINN | Approved | |
| 04/04/2019 | ELECTRIC - ABOVE CEILING | DQUINN | Approved | |
| 04/04/2019 | ELECTRIC - INTERMEDIATE | DQUINN | Approved | |
| 04/08/2019 | PLUMBING - INTERMEDIATE | AKLEINSORGE | Approved | |
| 05/01/2019 | ELECTRIC - FINAL | DQUINN | Approved | Ok for letter of completion upon approval of all entities. Existing fire riser room alarm, for entire strip mall needs work, not pertaining to this ti. |
| 05/01/2019 | BUILDING - FINAL | DQUINN | Approved | Ok for letter of completion upon approval of all entities. Existing fire riser room alarm, for entire strip mall needs work, not pertaining to this ti. |
| 05/01/2019 | PLUMBING - FINAL | DQUINN | Approved | Ok for letter of completion upon approval of all entities. Existing fire riser room alarm, for entire strip mall needs work, not pertaining to this ti. |
| 05/01/2019 | ENGINEERING - FINAL | RLEDONNE | Approved |