Permit: T18FC00421
Permit Details
Apply Date:
05/21/2018
Applicant:
Description:
Fire Alarm & Detection Systems - New addressable fire alarm system; Fire Alarm Systems - New Sq Ft: 5647; Fire Alarm Systems - # New Stories: 1; Additional Plan Reviews: 1
Outstanding Inspections
Permit Status: Expired
Permit Number: T18FC00421
Permite Description: Fire Alarm & Detection Systems - New addressable fire alarm system; Fire Alarm Systems - New Sq Ft: 5647; Fire Alarm Systems - # New Stories: 1; Additional Plan Reviews: 1
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/07/2018 | COT - FCON - Alarm - Final | N/A | Re-inspection required | {Activity date: 08/07/2018; Status: Denied; Inspector: jvincent; Comment: Entered by JVINCEN1 - Need to test the following zones. They did not report. CO2 high CO2 power loss (primary and secondary) smoke alarm RTU's FACP power loss Hood Possibly some others. Should conduct an entire fire alarm final to verify all signals.} |