Permit Details

Status:
Final
Type:
Flammable & Combustible Liquid
Address NEW:
6310 E GOLF LINKS RD
Apply Date:
05/15/2018
Applicant:
E P A BUSINESS SOLUTIONS INC
Description:
CIRCLE K #1634 - Replace Six (6) existing Dispenser Containment Sumps with new sumps
Contractors:
  • E P A BUSINESS SOLUTIONS INC

Completed Inspections

Permit Status: Final
Permit Number: T18FC00412
Permit Description: CIRCLE K #1634 - Replace Six (6) existing Dispenser Containment Sumps with new sumps
Total Completed Inspections - 2
Date Description Inspector Results Comments
10/30/2018 FUEL TANK FINAL 791-4502 jhinric1 Approved UDC's passed hydrostatic test. Secondary and primary lines passed pressure test. All fittings passed soap and water test.
10/30/2018 FUEL TANK FINAL 791-4502 jhinric1 Approved UDC's did not pass 1 hr hydrostatic test. New UDC's shall be installed.