Permit Details

Status:
Expired
Type:
Fire Construction Permit
Apply Date:
05/02/2018
Applicant:
Description:
Automatic Fire Extingshing Sys - BLDG #2 - INSTALL NEW FIRE SPRINKLER SYSTEM; Commercial Fire Sprinkler Systems - Standpipe New Outlets: 16; Additional Inspections: 5

Outstanding Inspections

Permit Status: Expired
Permit Number: T18FC00372
Permite Description: Automatic Fire Extingshing Sys - BLDG #2 - INSTALL NEW FIRE SPRINKLER SYSTEM; Commercial Fire Sprinkler Systems - Standpipe New Outlets: 16; Additional Inspections: 5
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
05/14/2019 COT - FCON - Sprinkler - Final N/A Partial Pass {Activity date: 05/14/2019; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - Tested the fire pump. The fire pump passed the inspection, however, the signals could not be verifyed to the fire alarm system so the fire pump is locked out until the signals can be confirmed.
Need to verify that the fire pump, water flow and tamper signals are reportting off site prior to approving a TCO for fixturing of the building.}

Completed Inspections

Permit Status: Expired
Permit Number: T18FC00372
Permit Description: Automatic Fire Extingshing Sys - BLDG #2 - INSTALL NEW FIRE SPRINKLER SYSTEM; Commercial Fire Sprinkler Systems - Standpipe New Outlets: 16; Additional Inspections: 5
Total Completed Inspections - 1
Date Description Inspector Results Comments
04/17/2019 FCON – OH Piping & Hydro Passed {Activity date: 04/17/2019; Status: Approved; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - All floors have now been completed for OH Piping & Hydro.} ; {Activity date: 10/11/2018; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by CBASALD1 - Bldg 2, Level 1. Inspected 6 units on the south side.} ; {Activity date: 10/23/2018; Status: Partial Approval; Inspector: jvincent; Comment: Entered by CBASALD1 - Bldg 2, Level 1. Rooms 2101-2107.} ; {Activity date: 01/03/2019; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Bldg 2, Level 6. Rooms 2602-2607 & 2613, 2615, 2616, 2618.} ; {Activity date: 04/16/2019; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Hydro test for Standpipes.} ; {Activity date: 03/26/2019; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Bldg 2, Level 4 Parking Garage} ; {Activity date: 02/07/2019; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Bldg 2, Level 6. Area B Amenities.} ; {Activity date: 02/07/2019; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Bldg 2, Level 6. Rooms 2611-2612.} ; {Activity date: 01/31/2019; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Bldg 2, Level 8. Rooms 2802-2808 & 2811-1818.} ; {Activity date: 01/23/2019; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Bldg 2, Level 7. Rooms 2702-2708 & 2711-2718.} ; {Activity date: 12/27/2018; Status: Partial Approval; Inspector: jvincent; Comment: Entered by JVINCEN1 - OH/hydro approved for 2501-2507, 2513-2518.} ; {Activity date: 12/11/2018; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - 4th floor OH Hydro @ 205 psi - Approved} ; {Activity date: 11/15/2018; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Bldg 2, Level 3. Rooms 2301-2307 & 2313-2318.} ; {Activity date: 10/30/2018; Status: Partial Approval; Inspector: CBASALDUA; Comment: Entered by CBASALD1 - Bldg 2, Level 2. Rooms 2201-2207 & 2213-2218.}

Documents

File Name Document Type  
001_FP-1.TIF FIRE PLANS VIEW
002_FP-2.TIF FIRE PLANS VIEW
003_FP-3.TIF FIRE PLANS VIEW
004_FP-4.TIF FIRE PLANS VIEW
005_FP-5.TIF FIRE PLANS VIEW
006_FP-6.TIF FIRE PLANS VIEW
007_FP-7.TIF FIRE PLANS VIEW
008_FP-8.TIF FIRE PLANS VIEW
009_FP-9.TIF FIRE PLANS VIEW
010_FP-10.TIF FIRE PLANS VIEW
011_FP-11.TIF FIRE PLANS VIEW
012_FP-12.TIF FIRE PLANS VIEW
013_FP-13.TIF FIRE PLANS VIEW
014_FP-14.TIF FIRE PLANS VIEW
015_FP-15.TIF FIRE PLANS VIEW
016_FP-16.TIF FIRE PLANS VIEW
017_FP-17.TIF FIRE PLANS VIEW
018_FP-18.TIF FIRE PLANS VIEW
019_FP-19.TIF FIRE PLANS VIEW
020_FP-20.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW
HYDRALIC CALS.PDF DOCUMENTS VIEW
HYDRALIC CALCS PT2.PDF DOCUMENTS VIEW