Permit: T18FC00359
Permit Details
Apply Date:
04/27/2018
Applicant:
CUTLER FIRE PROTECTION INC ,
Description:
Install new sprinkler System
Contractors:
- CUTLER FIRE PROTECTION INC ,
Completed Inspections
Permit Status: Final
Permit Number: T18FC00359
Permit Description: Install new sprinkler System
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/23/2018 | FIRE SPKLR - OH PIPING & HYDRO | jvincent | Approved | 1) OH/HYDRO approved 2) will need as builts 3) will verify double back flows included in calcs 4) resolve issues in east stairwell, coverage. 5) may be required to upsize drain size for full forward backflow annual test. |
11/27/2018 | FIRE SPKLR - UG, PIPING, HYDRO | JPEELDAVIS | Approved | Still need to perform the flush prior to riser connection |
06/20/2019 | FIRE SPKLR - FINAL | MRoss | Approved |