Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T18FC00315
Permit Details
Apply Date:
04/13/2018
Applicant:
Description:
Fire Alarm & Detection Systems - Add to Existing Voice system; Fire Alarm Systems - New Sq Ft: 10500; Inspections Performed Outside Normal Business Hours: 2
Outstanding Inspections
Permit Status: Expired
Permit Number: T18FC00315
Permite Description: Fire Alarm & Detection Systems - Add to Existing Voice system; Fire Alarm Systems - New Sq Ft: 10500; Inspections Performed Outside Normal Business Hours: 2
Total Outstanding Inspections - 1
Last Inspection Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2018 | COT - FCON - Alarm - Final | N/A | Partial Pass | {Activity date: 08/30/2018; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - Curtains for the elevator 4th floor worked good. Reset automatically with the fire alarm reset. Stairwell door did not unlatch on alarm.} ; {Activity date: 05/14/2018; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - Move and or correct the candella on speaker strobe north corridor for proper coverage. Need to test the elevator curtains.} |