Permit Details

Status:
Expired
Type:
Fire Construction Permit
Address:
3025 S KINO PW
Apply Date:
02/27/2018
Applicant:
Description:
Automatic Fire Extingshing Sys - INSTALLING FIRE SPRINKLERS

Outstanding Inspections

Permit Status: Expired
Permit Number: T18FC00173
Permite Description: Automatic Fire Extingshing Sys - INSTALLING FIRE SPRINKLERS
Total Outstanding Inspections - 1
Last Inspection Date Description Inspector Results Comments
05/04/2018 COT - FCON - Sprinkler - Final N/A Partial Pass {Activity date: 05/04/2018; Status: Partial Approval; Inspector: jvincent; Comment: Entered by JVINCEN1 - Still need full sprink final. These are notes from OH.
1) Add bracing to top of 6" riser on upper floor.
2) Add missing FDC.
3) Add bracing to riser in riser room.
4) Knox FDC plugs. (they have been ordered)
5) Mount spare head box, calc plate.}

Completed Inspections

Permit Status: Expired
Permit Number: T18FC00173
Permit Description: Automatic Fire Extingshing Sys - INSTALLING FIRE SPRINKLERS
Total Completed Inspections - 1
Date Description Inspector Results Comments
05/04/2018 FCON – OH Piping & Hydro Passed {Activity date: 05/04/2018; Status: Approved; Inspector: jvincent; Comment: Entered by JVINCEN1 - }