Permit Details

Status:
Expired
Type:
Fire Construction Permit
Address NEW:
3510 N CRAYCROFT RD
Apply Date:
02/01/2018
Applicant:
Description:
Automatic Fire Extingshing Sys - BLDG 9 - MAINTENANCE - 7 NEW SPRINKLERS

Outstanding Inspections

Permit Status: Expired
Permit Number: T18FC00106
Permite Description: Automatic Fire Extingshing Sys - BLDG 9 - MAINTENANCE - 7 NEW SPRINKLERS
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
08/14/2019 COT - FCON - Sprinkler - Final N/A Partial Pass {Activity date: 08/14/2019; Status: Partial Approval; Inspector: Mross; Comment: Entered by MROSS2 - -Provide clearance around riser through concrete
-Install test and main drain signs on riser
-Bell not operational at time of inspection}
08/30/2018 FCON – OH Piping & Hydro N/A Partial Pass {Activity date: 08/30/2018; Status: Partial Approval; Inspector: jvincent; Comment: Entered by JVINCEN1 - OH/hydro passed. Need to move a couple heads. Garage door heads too close to other pendents.}