Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T18CM02938
Permit Details
Status:
C of o
Type:
COMMERCIAL ALTERATION
Address:
750 E FOOTHILLS DR
Address NEW:
750 E FOOTHILLS DR
Apply Date:
04/19/2018
Applicant:
MAHER, JOSEPH SAID JR
Description:
ASSISTED LIVING
Architects:
- MAHER, JOSEPH SAID JR
Contractors:
- DM GIN LLC
Permit Reviews
Permit Number - T18CM02938
Permit Status: C of o
Permit Description: ASSISTED LIVING
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 04/19/2018 | PLANS OK TO SUBMIT - COMM | 04/20/2018 | COMPLETED |
| 05/31/2018 | 3RD PARTY REVIEW - COMMERCIAL TI | 06/01/2018 | COMPLETED |
| 06/01/2018 | POST 3RD PARTY REVIEW | 07/03/2018 | COMPLETED |
| 11/02/2018 | 3RD PARTY REVIEW - REVISION/OTHER | 11/08/2018 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T18CM02938
Permit Status: C of o
Permit Description: ASSISTED LIVING
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 04/19/2018 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: C of o
Permit Number: T18CM02938
Permit Description: ASSISTED LIVING
Total Completed Inspections - 24
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2018 | PLUMBING - ROUGH, SOIL | JBURGE | Approved | EXTERIOR WASTE LINES TO HCS. OK TO COVER PROGRESS AREA. |
| 08/03/2018 | EXCAVATION/LAYOUT REBAR & ZON | BJONES | Approved | NO EXCAVATIONS WERE FOUND ON SITE EXCEPT UNDERGROUND PLUMBING TRENCHES |
| 08/03/2018 | MECHANICAL - ABOVE CEILING | BJONES | Approved | |
| 08/03/2018 | ELECTRIC - ABOVE CEILING | BJONES | Approved | SELF NAIL PLATES MAY NOT BE USED WHERE LUMBER IS NOTCHED. REPLACE WITH STRAPS USING NAILS OR SCREWS FOR ATTACHEMENT |
| 08/03/2018 | BUILDING ABOVE CEILING | BJONES | Approved | |
| 08/03/2018 | PLUMBING - ABOVE CEILING | BJONES | Approved | INSULATE BETWEEN FERRIS AND NON FERRIS METALS IN CEILING |
| 08/03/2018 | PLUMBING - PRE SLAB | BJONES | Approved | REMOVE NEOPREME JIM CAP AND INSTALL ABS GLUE CAP BELOW GRADE IN CENTER BATH. |
| 08/03/2018 | PLUMBING - INTERMEDIATE | BJONES | Approved | PLATE STRAPS REQUIRED FOR NOTCHED PLATES, STUDS, AND SIMULAR. INSTALL INSULATING MATERIAL BETWEEN THE DISIMULAR METALS IN CEILING OF CENTER BATHROOM. THE FIRE SPRINKLER PIPING IS TOUCHING THE COPPER WATER PIPE. SEND PICTURES OF REPAIR |
| 08/27/2018 | FRAMING | ESTEVEN1 | Approved | APPROVED |
| 08/27/2018 | ELECTRIC - INTERMEDIATE | ESTEVEN1 | Approved | APPROVED |
| 08/31/2018 | SHEET ROCK NAILING | DFLORES2 | Approved | IVRS - Inspection :* |
| 08/31/2018 | FIREWALL/FIREBARRIER/FIRESTOP | DFLORES2 | Approved | IVRS - Inspection :* |
| 09/04/2018 | MECHANICAL - INTERMEDIATE | ESTEVENS | Approved | |
| 11/16/2018 | PLUMBING - FINAL | JBURGE | Approved | |
| 11/16/2018 | ELECTRIC - FINAL | JBURGE | Approved | |
| 11/20/2018 | MECHANICAL - HOOD SYSTEMS | ESTEVENS | Approved | |
| 11/20/2018 | MECHANICAL - HOODS | ESTEVENS | Approved | |
| 11/20/2018 | FIRE - ALARM FINAL | CBASALDUA | Approved | |
| 11/20/2018 | FIRE - KITCHEN EXH HOOD FINAL | CBASALDUA | Approved | |
| 11/20/2018 | FIRE SPKLR - FINAL | CBASALDUA | Approved | |
| 11/26/2018 | BUILDING - FINAL | DMCCARTHY | Approved | pending fire Marshall’s, and garbage disposal deleted in kitchen. |
| 11/26/2018 | FIRE - FINAL | jvincent | Approved | |
| 11/28/2018 | MECHANICAL - FINAL | RSHERRY | Approved | REVIEW OF AIR BALANCE REPORT COMPLETED |
| 11/30/2018 | ENGINEERING - FINAL | BBENEDON | Approved | Existing accessible parking and access is not in compliance with currant requirements. |