Permit Details

Status:
Final
Type:
State Lic Facls Annual Insp
Address:
5910 E 5TH ST
Apply Date:
04/18/2017
Applicant:
ST. PAUL'S ACADEMY
Description:
PRESCHOOL 20 PERSONS

Completed Inspections

Permit Status: Final
Permit Number: T17FO00322
Permit Description: PRESCHOOL 20 PERSONS
Total Completed Inspections - 1
Date Description Inspector Results Comments
05/17/2017 FIRE INSP - STATE LICENSE nsprenger Approved 2012 IFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring.
1) You shall remove the extension cord powering the computer in the office. You may use a UL listed power strip with over surge protection.

2012 IFC 1006.1 Illumination required. The means of egress, including
the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
2) The 2 Emergency lights in the dining are not working. You shall cause them to operate as stated above.

2012 IFC 901.6.2 Records. Records of all system inspections, tests and
maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request.
1) You shall provide the inspector with a copy of:
a) your most recent fire alarm system annual report
b) your most recent sprinkler system annual report

2012 IFC 113 amendment Table 113 - Permit Fee Table. An operational permit shall be obtained for a state licensed facility.
1) You shall submit a permit application and pay the required permit fee before the operational permit for a state licensed facility will be issued.