Permit: T17FC00743
Permit Details
Apply Date:
09/12/2017
Applicant:
Description:
Fire Alarm & Detection Systems - FIRE ALARM SYSTEMS; Fire Alarm Systems - New Sq Ft: 42667; Fire Alarm Systems - # New Stories: 2
Outstanding Inspections
Permit Status: Expired
Permit Number: T17FC00743
Permite Description: Fire Alarm & Detection Systems - FIRE ALARM SYSTEMS; Fire Alarm Systems - New Sq Ft: 42667; Fire Alarm Systems - # New Stories: 2
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2018 | COT - FCON - Alarm - Final | N/A | Partial Pass | {Activity date: 01/11/2018; Status: Partial Approval; Inspector: JPEELDAVIS; Comment: Entered by JPEELDA1 - Need to add low frequency sounders to room 202, 201 and 153 to accomodate the living room with a sleeper sofa. Sounder in room 254 needs to be repaired. Plastic cover in room 220 needs to be replaced. Asbuilt drawings will be required. Only need to test the above mentioned rooms once they are completed. Due to the gem and mineral show they will have until March 30th to complete these items.} |