Permit Details

Status:
Final
Type:
Automatic Fire Extingshing Sys
Apply Date:
04/04/2017
Applicant:
ALC UNDERGROUND LLC
Description:
EXTEND 4" FIRE LINE FROM PROPERTY LINE TO FIRE RISER AT EACH BUILDING (UNDERGROUND ONLY)
Contractors:
  • ALC UNDERGROUND LLC

Completed Inspections

Permit Status: Final
Permit Number: T17FC00264
Permit Description: EXTEND 4" FIRE LINE FROM PROPERTY LINE TO FIRE RISER AT EACH BUILDING (UNDERGROUND ONLY)
Total Completed Inspections - 2
Date Description Inspector Results Comments
05/09/2017 FIRE SPKLR - UG PIPING FLUSH JPEEL-DAVIS Approved 205 & 207 PSI
Flushed both risers
05/09/2017 FIRE SPKLR - UG, PIPING, HYDRO JPEEL-DAVIS Approved

Documents

File Name Document Type  
001_FIRE PLAN.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW