Permit Details

Status:
Expired
Type:
SINGLE FAMILY ALTERATION
Address:
5402 E LESTER ST
Address NEW:
5402 E LESTER ST
Apply Date:
01/13/2017
Applicant:
N/A
Description:
(T16DV08549) REMODEL SFR
Contractors:
  • PIMA VENTURES LLC

Permit Reviews

Permit Number - T17CM00325
Permit Status: Expired
Permit Description: (T16DV08549) REMODEL SFR
Start Date Submittal Complete Date Status  
01/13/2017 RESIDENTIAL - BLDG/WWM 02/08/2017 ACTIVE Review Details
01/13/2017 RESIDENTIAL - BLDG/ZONING-WALKTHRU 01/13/2017 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T17CM00325
Permit Status: Expired
Permit Description: (T16DV08549) REMODEL SFR
Total Outstanding Activity Conditions - 1
Date Name
01/13/2017 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T17CM00325
Permite Description: (T16DV08549) REMODEL SFR
Total Outstanding Inspections - 5
Last Inspection Date Description Inspector Results Comments
03/03/2017 ELECTRIC - INTERMEDIATE N/A Denied NO ELECTRICAL PLAN ON SITE. ALL ELECTRICAL WIRING IS COVERED BY DRYWALL.REMOVE DRYWALL OR HAVE A CERTIFIED ELECTRICIAN CERTIFY, ON COMPANY LETTERHEAD THAT ALL ELECRTICAL WORK IS PER 2012 IRC CODE
04/19/2017 BUILDING - FINAL N/A Denied OUTLET IN KITCHEN AND LIVING ROOM IS NOT WORKING
GFCI IN KITCHEN WONT RESET
LAUNDRY ROOM OUTLET IS NOT SECURED
BATHROOM OUTLET IS WIRED INCORRECT
NO LADDER TO ROOF
OUTSIDE OUTLETIN NOTGFCI
NO ANTI-SIPHON HOSE BIBS
1" CLEARANCE IS REQUIRED AROUND THE WATER HEATER B-VENT
STOP INSPECTION
04/19/2017 ELECTRIC - FINAL N/A Denied OUTLET IN KITCHEN AND LIVING ROOM IS NOT WORKING
GFCI IN KITCHEN WONT RESET
LAUNDRY ROOM OUTLET IS NOT SECURED
BATHROOM OUTLET IS WIRED INCORRECT
NO LADDER TO ROOF
OUTSIDE OUTLETIN NOTGFCI
NO ANTI-SIPHON HOSE BIBS
1" CLEARANCE IS REQUIRED AROUND THE WATER HEATER B-VENT
STOP INSPECTION
04/19/2017 PLUMBING - FINAL N/A Denied OUTLET IN KITCHEN AND LIVING ROOM IS NOT WORKING
GFCI IN KITCHEN WONT RESET
LAUNDRY ROOM OUTLET IS NOT SECURED
BATHROOM OUTLET IS WIRED INCORRECT
NO LADDER TO ROOF
OUTSIDE OUTLETIN NOTGFCI
NO ANTI-SIPHON HOSE BIBS
1" CLEARANCE IS REQUIRED AROUND THE WATER HEATER B-VENT
STOP INSPECTION
04/19/2017 MECHANICAL - FINAL N/A Denied OUTLET IN KITCHEN AND LIVING ROOM IS NOT WORKING
GFCI IN KITCHEN WONT RESET
LAUNDRY ROOM OUTLET IS NOT SECURED
BATHROOM OUTLET IS WIRED INCORRECT
NO LADDER TO ROOF
OUTSIDE OUTLETIN NOTGFCI
NO ANTI-SIPHON HOSE BIBS
1" CLEARANCE IS REQUIRED AROUND THE WATER HEATER B-VENT
STOP INSPECTION

Completed Inspections

Permit Status: Expired
Permit Number: T17CM00325
Permit Description: (T16DV08549) REMODEL SFR
Total Completed Inspections - 4
Date Description Inspector Results Comments
02/17/2017 MECHANICAL - INTERMEDIATE ESTEVEN1 Approved APPROVED
02/17/2017 FRAMING ESTEVEN1 Approved APPROVED
03/03/2017 ELECTRIC - SERVICE UPGRADE ESTEVEN1 Approved APPROVED
03/06/2017 TEP CLEARANCE - AM ESTEVENS Approved INCR

Documents

File Name Document Type  
001_PLOT PLAN.TIF CONSTRPLANS VIEW
002_FLOOR PLAN.TIF CONSTRPLANS VIEW
003_PLUMBING PLAN.TIF CONSTRPLANS VIEW
004_MECHANICAL PLAN.TIF CONSTRPLANS VIEW
005_ELECTRICAL PLAN.TIF CONSTRPLANS VIEW
None DOCUMENTS VIEW