Permit: T16CM07078
Permit Details
Apply Date:
09/13/2016
Applicant:
BRODSKY SERVICE
Description:
REPL EXHAUST FAN
Contractors:
- BRODSKY SERVICE
Permit Reviews
Permit Number - T16CM07078
Permit Status: Expired
Permit Description: REPL EXHAUST FAN
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 09/13/2016 | WALK THRU - COMM | 09/27/2016 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T16CM07078
Permit Status: Expired
Permit Description: REPL EXHAUST FAN
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/13/2016 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T16CM07078
Permite Description: REPL EXHAUST FAN
Total Outstanding Inspections - 3
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2017 | MECHANICAL - FINAL | N/A | Not ready for Inspection | please correct address to 6211 e. 22nd, provide rooof access, complete electrcal, ansul system, and gas piping with shut-off valve, need drawing showing kitchen equipment, going under hood. will need test and balance certification. Q; are you using temperature sensor - or - shutoff gas interlock on this hood, do you have 18 in. to combustables from back wall and ceiling to this hood. incomplete inspection. |
| 06/19/2017 | MECHANICAL - INTERMEDIATE | N/A | Not ready for Inspection | warning, next not ready = re-fee |
| 11/28/2016 | MECHANICAL - HOODS | N/A | Not ready for Inspection | no inspectionIVRS - Inspection :* |