Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Expired
Type:
SINGLE FAMILY OTHER
Address:
3332 N ROMERO RD
Address NEW:
3332 N ROMERO RD
Apply Date:
02/16/2016
Applicant:
HENRY BABEL
Description:
ELECTRIC RECONNECT

Outstanding Activity Conditions

Permit Number - T16CM01088
Permit Status: Expired
Permit Description: ELECTRIC RECONNECT
Total Outstanding Activity Conditions - 1
Date Name
02/16/2016 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Outstanding Inspections

Permit Status: Expired
Permit Number: T16CM01088
Permite Description: ELECTRIC RECONNECT
Total Outstanding Inspections - 2
Last Inspection Date Description Inspector Results Comments
09/09/2016 ELECTRIC - RECONNECT N/A Denied 30A RECEPTICLE IS BROKEN,
OPEN HOLE WITH SHARP EDGES WITH DROP CORD PROTRUDING,
BREAKERS NOT SEATED CORRECTLY IN BOX,
60A RATED CORD WIRED TO A 100A BREAKER.
09/09/2016 ELECTRIC - FINAL N/A Not ready for Inspection

Documents

File Name Document Type  
None DOCUMENTS VIEW