Permit: T16CM00067
Permit Details
Apply Date:
01/06/2016
Applicant:
HICKEY THOMAS J & LINDEN C JT/RS
Description:
T15DV06178 FIRE DAMAGE REPAIR AND WATER HEATER VENTING REPLACEMENT
Contractors:
- HICKEY CUSTOM POOLS INC
Permit Reviews
Permit Number - T16CM00067
Permit Status: Expired
Permit Description: T15DV06178 FIRE DAMAGE REPAIR AND WATER HEATER VENTING REPLACEMENT
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 01/06/2016 | RESIDENTIAL - BLDG/ZONING-WALKTHRU | 01/14/2016 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T16CM00067
Permit Status: Expired
Permit Description: T15DV06178 FIRE DAMAGE REPAIR AND WATER HEATER VENTING REPLACEMENT
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 01/06/2016 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T16CM00067
Permite Description: T15DV06178 FIRE DAMAGE REPAIR AND WATER HEATER VENTING REPLACEMENT
Total Outstanding Inspections - 2
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/23/2016 | BUILDING - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL PROVIDE TRIM PLATES FOR ALL RECEPTICAL BOXES THAT ARE MISSING. 2- SHALL LOCATED THE GAS WATER HEATER MINIMUM OF 18" ABOVE THE FINISH FLOOR IN GARAGE. 3- SHALL PIPE THE WATER HEATER T & P DRAIN TO DAYLIGHT AND TERMINATE IT 6" ABOVE SUB GRADE. 4- SHALL PROVIDE A MINIMUM OF 6" OF CLEARANCE FROM COMBUSTIONABLE MATERIAL FOR THE SINGLE WALL WATER HEATER FLU VENT. 4 SHALL PROVIDE PROTECTION FOR THE WATER HEATER. * |
| 08/23/2016 | ELECTRIC - FINAL | N/A | Denied | IVRS - Inspection : See detailed listing on site.| 999 * |
Completed Inspections
Permit Status: Expired
Permit Number: T16CM00067
Permit Description: T15DV06178 FIRE DAMAGE REPAIR AND WATER HEATER VENTING REPLACEMENT
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2016 | ELECTRIC - INTERMEDIATE | RMORENO | Approved | IVRS - Inspection :* |
| 08/05/2016 | PLUMBING - FINAL | RMORENO | Approved | IVRS - Inspection :* |
| 08/05/2016 | FRAMING | RMORENO | Approved | IVRS - Inspection :* |