Permit: T15CM07387
Permit Details
Apply Date:
10/23/2015
Applicant:
JIM FOSTER
Description:
REPLACE GAS LINE
Contractors:
- PIONEER PLUMBING INC ,
Outstanding Activity Conditions
Permit Number - T15CM07387
Permit Status: Expired
Permit Description: REPLACE GAS LINE
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/23/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T15CM07387
Permite Description: REPLACE GAS LINE
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2015 | PLUMBING - FINAL | N/A | Denied | GAS PIPING PASSING THROUGH MASONRY WALL SHALL BE SLEEVED, THEN SEALED. REMOVE ALL CONCRETE FRPM PIPE. SEAL OTHER PENETRATIONS. ADD UNIT NUMBER TO PERMIT. REMOVE PIPING A METER NOT SHOWN ON PLAN. CARBON MONOXIDE DETECTOR IS REQUIRED. SERVICE VENT CONNECTIONS, CHECK SAFETY VALVE. PROVIDE ROOF ACCESS. RPOVIDE PERMIT FOR FURNACE INSTALL OR VERIFY APPROVAL. YOU MAY NOT CONNECT PIPING NOT SHOWN ON PLAN. |
Completed Inspections
Permit Status: Expired
Permit Number: T15CM07387
Permit Description: REPLACE GAS LINE
Total Completed Inspections - 1
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/30/2015 | PLUMBING - GAS PRESSURE TEST | BBENEDOI | Approved | IVRS - Inspection :* |