| 09/08/2015 | WALK THRU - RES | 09/08/2015 | COMPLETED |
| 10/28/2015 | REVISION - - 1ST | 11/10/2015 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T15CM06246
Permit Status: Expired
Permit Description: UPGRADE TO 200AMP MAIN PANEL
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 09/08/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: Expired
Permit Number: T15CM06246
Permite Description: UPGRADE TO 200AMP MAIN PANEL
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2016 | ELECTRIC - FINAL | N/A | Partial Approval | 1. 2 GROUND RODS AND #6 WIRE 2. ADDRESS LABEL MISSING 3. OLD SERVICE NOT TO BE USED AS SUB PANEL OR J BOX 4. SUB PANEL AT GARAGE MISSING GROUND BAR 5. IS RISER WIRE 4/0 ALUMINUM |
Completed Inspections
Permit Status: Expired
Permit Number: T15CM06246
Permit Description: UPGRADE TO 200AMP MAIN PANEL
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2016 | ELECTRIC - SERVICE UPGRADE | RMORENO | Approved | IVRS - Inspection :* |
| 01/26/2016 | ELECTRIC - SERVICE RELOCATION | RMORENO | Approved | IVRS - Inspection :* |
| 01/27/2016 | TEP CLEARANCE - AM | RMORENO | Approved | INCR |