Permit: T15CM03554
Permit Details
Apply Date:
05/29/2015
Applicant:
KIRKE W. RICE, ARCHITECT PLLC
Description:
OFF SITE CANNIBUS CULTIVATION
Contractors:
- HALL DESIGN BUILD CONSTRUCTION
Permit Reviews
Permit Number - T15CM03554
Permit Status: C of o
Permit Description: OFF SITE CANNIBUS CULTIVATION
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 05/29/2015 | COMMERCIAL - BLDG/FIRE/ZONING/ENG | 06/04/2015 | COMPLETED |
| 06/04/2015 | COMMERCIAL - BLDG/FIRE/ZONING/ENG | 06/04/2015 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T15CM03554
Permit Status: C of o
Permit Description: OFF SITE CANNIBUS CULTIVATION
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 05/29/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Outstanding Inspections
Permit Status: C of o
Permit Number: T15CM03554
Permite Description: OFF SITE CANNIBUS CULTIVATION
Total Outstanding Inspections - 1
| Last Inspection Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/11/2015 | FIRE - FINAL | N/A | Denied | 1. NEED ADDRESS NUMBERS THAT COMPLY WITH PIMA COUNTY ADDRESSING CODE - CANT BE SEEN FROM STREET 2. SPRINKLER PIPE IN RECEPTION AREA NEEDS TO BE CUTCUT BACK AND SPRINKLER HEADS FLUSH WITH DROP CEILING. 3. NEED LIGHTED EXIT SIGNS THROUGH OUT 4. EMERGENCY LIGHT/EXIT SIGN NEED TO OPERATE WHEN AC POWER IS OFF ( BATTERY BACK UP) 5. REMOVE EXIT SIGN OVER CULTIVATION DO TO THE LOUNG AREA. NOT AN EXIT. 6. ALL FIRE EXTINGUISHERS MUST BE TAGGED AS INSPECTED AND PASSING WITH IN THE LAST YEAR. 7. THE SPRINKLER RISER DOES NOT HAVE A SPEC/DESIGN PLATE ON IT. 8. NEED EMERGENCY LIGHTIN IN THE CULTIVATION ROOM. 9. 9. THUMB TURN LOCK ON SOUTH EXIT DOOR FROM CULTIVATION ROOM MUST BE BETWEEN 34" - 48" OF THE FINISHED FLOOR. 10. PROVIDE A COPY OF MOST RECENT SPRINKLER SYSTEM INSPECTION WITH DOCUMENTATION OF LAST CHECK VALVE INSEPCTION. 11. MUST HAVE EMERGENCY LIGHTING IN RESTROOM 12. LICENSED SPRINKLER CONTRACTOR MUST PULL A PERMIT FOR AND DRAW UP PLANS TO INSTALL AND MOVE HEADS AS NECESSARY FOR COVERAGE IN ( IT ROOM, IN RECEPTION AREA ON EAST SIDE OF NORTH WALL, RESTROOM HALLWAY, WOMENS RESTROOM). 13. MUST INSTALL A FIRE DEPARTMENT KEYED LOCK BOX ON OUTSIDE GATE WITH ACCESS KEYS TO SECURITY GATE, BUILDING, RISER ROOM. 14. MUST CREATE AN UNOBSTRUCTED AND UNOBSCURED PATH TO THE FIRE DEPARTMENT CONNECTIONS FROM THE ROAD. 15. MUST PLACE A SIGN THAT IS LEGIBLE FROM THE ROAD THAT STATES LOCATION OF THE FDC'S. |
Completed Inspections
Permit Status: C of o
Permit Number: T15CM03554
Permit Description: OFF SITE CANNIBUS CULTIVATION
Total Completed Inspections - 3
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/08/2015 | BUILDING - FINAL | JBURGE | Approved | IVRS - Inspection :* |
| 07/30/2015 | ENGINEERING - FINAL | EDUARTE | Approved | |
| 07/30/2015 | ZONING - FINAL | EDUARTE | Approved |