Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T15BU01339
Permit Details
Apply Date:
11/17/2015
Applicant:
DIRTWORKS CONTRACTING INC
Description:
SPRINKLER
Contractors:
- DIRTWORKS CONTRACTING INC
Outstanding Activity Conditions
Permit Number - T15BU01339
Permit Status: Closed
Permit Description: SPRINKLER
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 11/17/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Closed
Permit Number: T15BU01339
Permit Description: SPRINKLER
Total Completed Inspections - 2
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/19/2015 | FIRE SPKLR - UG, PIPING, HYDRO | CSCHULTZ | Approved | 200 PSI for 2 hours both supply line and FDC line |
| 12/21/2015 | FIRE SPKLR - UG PIPING FLUSH | nsprenger | Approved | Flushed clean. Still need 'Contractors Material and TEst Certificate for undergroung Piping' before approval on Underground/Flush. I gave my email / Fax for submission. |