Permit: T15BU01221
Permit Details
Apply Date:
10/20/2015
Applicant:
METRO TUCSON EXPEDITING & DEVELOPMENT
Description:
NEW TANKS
Contractors:
- UNITED BUILDERS LLC
Permit Reviews
Permit Number - T15BU01221
Permit Status: Final
Permit Description: NEW TANKS
| Start Date | Submittal | Complete Date | Status |
|---|---|---|---|
| 10/21/2015 | TANKS | 07/13/2016 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T15BU01221
Permit Status: Final
Permit Description: NEW TANKS
Total Outstanding Activity Conditions - 1
| Date | Name |
|---|---|
| 10/20/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T15BU01221
Permit Description: NEW TANKS
Total Completed Inspections - 6
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/02/2016 | FUEL TANK TIGHTNESS AND HOLE | jhinric | Approved | jhinric - 2 UST's installed. 1 - split diesel and premium, 1 unleaded. tanks level with proper bedding and no damage. shipping paper #'s matched tank #'s |
| 04/06/2016 | ELECTRIC - FINAL | RMORENO | Approved | |
| 04/06/2016 | ELECTRIC - INTERMEDIATE | RMORENO | Approved | |
| 04/06/2016 | ELECTRIC - UNDERGROUND | RMORENO | Approved | |
| 04/26/2016 | FUEL PIPING INSP. & PRESS TEST | jhinric | Approved | jhinric - primary and secondary lines held pressure. all joints and runs soaped with no visible leaks. water in sumps showed no leaks. |
| 07/12/2016 | FUEL TANK FINAL 791-4502 | jhinric | Approved | Jhinric - e stop working, shear valves intact, fire extinguishers placed, emergency telephone placed, tested, and works, sensors intact, signage intact |