Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T15BU01069
Permit Details
Apply Date:
09/15/2015
Applicant:
CUTLER FIRE PROTECTION INC ,
Description:
UG PIPING 83' OF 4" PIPE
Contractors:
- CUTLER FIRE PROTECTION INC ,
Outstanding Activity Conditions
Permit Number - T15BU01069
Permit Status: Final
Permit Description: UG PIPING 83' OF 4" PIPE
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
09/15/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T15BU01069
Permit Description: UG PIPING 83' OF 4" PIPE
Total Completed Inspections - 3
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/10/2015 | FIRE SPKLR - UG, PIPING, HYDRO | CSCHULTZ | Approved | 200 PSI FOR 2 HOURS 2ND HALF APPROVED |
12/15/2015 | FIRE SPKLR - FINAL | CSCHULTZ | Approved | |
12/15/2015 | FIRE SPKLR - UG PIPING FLUSH | CSCHULTZ | Approved | Flushed for 2 mins Burlap sack for 1min showed clean |