Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit: T15BU00986
Permit Details
Apply Date:
08/26/2015
Applicant:
MIKE KELLOGG
Description:
497 NEW SPRINKLERS
Contractors:
- KELLOGG FIRE N WIRE INC ,
Outstanding Activity Conditions
Permit Number - T15BU00986
Permit Status: Final
Permit Description: 497 NEW SPRINKLERS
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
08/26/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T15BU00986
Permit Description: 497 NEW SPRINKLERS
Total Completed Inspections - 4
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/28/2015 | FIRE SPKLR - UG PIPING FLUSH | CSCHULTZ | Approved | Flush for 1 min and then use burlap sack and flush for 1 min again all clear |
11/06/2015 | FIRE SPKLR - UG, PIPING, HYDRO | nsprenger | Approved | Tested the section of underground under East easment behing building; leading up to riser in building. Pressured up at 10:30 am , read at 12:58 pm at 212 psi. ( Pipe is already backfilled - can't visualize). |
11/30/2015 | FIRE SPKLR - OH PIPING & HYDRO | CSCHULTZ | Approved | 200 PSI test for piping to front canopy sprinklers APPROVED |
12/15/2015 | FIRE SPKLR - FINAL | nsprenger | Approved |