Permit: T15BU00640
Permit Details
Apply Date:
06/09/2015
Applicant:
CINTAS FIRE PROTECTION
Description:
FIXED SYSTEM
Contractors:
- CINTAS FIRE PROTECTION
Permit Reviews
Permit Number - T15BU00640
Permit Status: Final
Permit Description: FIXED SYSTEM
Start Date | Submittal | Complete Date | Status |
---|---|---|---|
06/09/2015 | MECHANICAL | 06/11/2015 | COMPLETED |
Outstanding Activity Conditions
Permit Number - T15BU00640
Permit Status: Final
Permit Description: FIXED SYSTEM
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
06/09/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T15BU00640
Permit Description: FIXED SYSTEM
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/17/2015 | FIRE - KITCHEN EXH HOOD FINAL | nspreng1 | Approved | PULL STATION AND LINK PASSED. ALL GAS AND ELECTRIC UNDER HOOD SHUT DOWN. MAKE UP AIR SHUT DOWN AND EXHAUST STAYED ON. ALL NOZZLES ARE WITHIN DESIGN PER PLANS. HOOD SYSTEM IS TIED INTO ALARM SYSTEM AND NOTIFICATION DEVICES ALL ACITIVATED AND ALARM WAS RECIEVED AT THE PANEL AND THE MONITORING COMPANY AS AN 'ALARM' WITH A RESET. |