Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Apply Date:
06/09/2015
Applicant:
CINTAS FIRE PROTECTION
Description:
FIXED SYSTEM
Contractors:
  • CINTAS FIRE PROTECTION

Permit Reviews

Permit Number - T15BU00640
Permit Status: Final
Permit Description: FIXED SYSTEM
Start Date Submittal Complete Date Status  
06/09/2015 MECHANICAL 06/11/2015 COMPLETED Review Details

Outstanding Activity Conditions

Permit Number - T15BU00640
Permit Status: Final
Permit Description: FIXED SYSTEM
Total Outstanding Activity Conditions - 1
Date Name
06/09/2015 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T15BU00640
Permit Description: FIXED SYSTEM
Total Completed Inspections - 1
Date Description Inspector Results Comments
06/17/2015 FIRE - KITCHEN EXH HOOD FINAL nspreng1 Approved PULL STATION AND LINK PASSED.
ALL GAS AND ELECTRIC UNDER HOOD SHUT DOWN.
MAKE UP AIR SHUT DOWN AND EXHAUST STAYED ON. ALL NOZZLES ARE WITHIN DESIGN PER PLANS. HOOD SYSTEM IS TIED INTO ALARM SYSTEM AND NOTIFICATION DEVICES ALL ACITIVATED AND ALARM WAS RECIEVED AT THE PANEL AND THE MONITORING COMPANY AS AN 'ALARM' WITH A RESET.

Documents

File Name Document Type  
001_1 OF 2.TIF FIRE PLANS VIEW
002_2 OF 2.TIF FIRE PLANS VIEW
None DOCUMENTS VIEW