Permit: T15BU00170
Permit Details
Apply Date:
02/12/2015
Applicant:
ADVANCED PROTECHTION SYSTEMS A S INC
Description:
FIRE ALARM-WATERFLOW/TAMPER ONLY
Contractors:
- ADVANCED PROTECHTION SYSTEMS A S INC
Outstanding Activity Conditions
Permit Number - T15BU00170
Permit Status: Final
Permit Description: FIRE ALARM-WATERFLOW/TAMPER ONLY
Total Outstanding Activity Conditions - 1
Date | Name |
---|---|
02/12/2015 | PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION. |
Completed Inspections
Permit Status: Final
Permit Number: T15BU00170
Permit Description: FIRE ALARM-WATERFLOW/TAMPER ONLY
Total Completed Inspections - 1
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2015 | FIRE - ALARM FINAL | nsprenger | Approved | Approved Building 602 ( has alarm panel for both) flow alram 25 sec tamper alarm pull station alarm smoke alarm ..........all recieved by monitoring company Building 612 27 sec flow alarm tampler alarm All reported to monitoring company |