Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Details

Status:
Final
Type:
COMMERCIAL OTHER
Address NEW:
1455 S ALVERNON WY
Apply Date:
05/15/2014
Applicant:
COMPLETE FIRE PROTECTION INC
Description:
INSTALL 566 NEW FIRE SPRINKLERS
Contractors:
  • COMPLETE FIRE PROTECTION INC

Outstanding Activity Conditions

Permit Number - T14BU00509
Permit Status: Final
Permit Description: INSTALL 566 NEW FIRE SPRINKLERS
Total Outstanding Activity Conditions - 1
Date Name
05/15/2014 PLANS EXPIRE IN 180 DAYS FROM DATE OF SUBMITTAL. PERMITS EXPIRE IN 180 DAYS FROM DATE OF ISSUE OR LAST INSPECTION.

Completed Inspections

Permit Status: Final
Permit Number: T14BU00509
Permit Description: INSTALL 566 NEW FIRE SPRINKLERS
Total Completed Inspections - 2
Date Description Inspector Results Comments
07/21/2014 FIRE SPKLR - OH PIPING & HYDRO CSCHULTZ Approved OH 200 psi 2 hours Approved
Placement need to correct some areas noted on plans -
09/23/2014 FIRE SPKLR - FINAL CBASALDUA Approved 1. Water Flow #1 30 sec.
2. Water Flow #2 39 sec.
3. Main Drain # 1 70/55/70.
4. Main Drain #2 75/50/75.